NEW PHOTOVOLTAIC PITCHED ROOF MOUNTED SYSTEM - 32.190 KW DC/23.000 KW AC CONTRACTOR
& ENERGY STORAGE SYSTEM - 27 KWH |_JEMPIRESOLAR
90 CENTER RIDGE RD, EAST AURORA, NY 14052
NEW PV SYSTEM SPECIFICATIONS
SYSTEM SIZE: DC SIZE: 32.190 KW DC-(STC)
AC SIZE: 23.000 KW AC
ep SHEET INDEX EMPIRE SOLAR SOLUTIONS
MODULE: (74) HYUNDAI HIN-T435NF(BK) PV-01 COVER PAGE 2-8 JOHNES ST
INVERTER: (2) TESLA 1707000-XX-Y PV-02 SITE PLAN NEWBURGH, 12550
RSD'S: (29) TESLA MCI-2 HIGH CURRENT PV-03 ATTACHMENT PLAN & DETAILS PHONE - (845) 728-2165
PV-04 ELECTRICAL DIAGRAM LIC. NO. - WC-29806-H17
PV-05 NOTES
PV-06 WARNING LABELS
PV-07 INSTALLATION RESOURCE
EQUIPMENT DATASHEETS ATTACHED
APPLICABLE CODES
ALL WORK SHALL CONFORM TO THE FOLLOWING CODES:
2020 BUILDING CODE OF NEW YORK STATE
2020 RESIDENTIAL CODE OF NEW YORK STATE
LEGEND
2020 FIRE CODE OF NEW YORK STATE Wyssling Consulting, PLLC ~ PROPERTY LINE
2017 NATIONAL ELECTRICAL CODE 76 N. Meadowbrook Drive, Alpine UT
AS ADOPTED BY TOWN OF AURORA New York COA #0022571 => O- o - FENCE LINE
Signed 9/10/2025
Expires 7/31/2027
DESIGN CRITERIA oe
ROOF SURFACE TYPE: COMPOSITE SHINGLE —————E——— a PROJECT NAME & ADDRESS
ROOF FRAMING: 2"X6" RAFTER @ 24" OC THOMAS MILLER
BUILDING STORY: TWO_STORY - 50 CENTER RIDGE RD,
GROUND SNOW.LOAD* 35.PSF soe CT so5-41" EAST AURORA, NY 14052
WIND SPEED{(119)MPH—~
WIND EXPOSURE: C rH.
RISK CATEGORY: Il That
il Lim APN #: 142489A187020000201 7000
JSNOH JO LNOYS
AHJ: TOWN OF AURORA
PROJECT NOTES UTILITY: NEW YORK STATE
1.1.1 THIS PHOTOVOLTAIC (PV) & ENERGY STORAGE SYSTEM ELECTRIC & GAS
SHALL COMPLY WITH THE RELEVANT YEAR OF THE NATIONAL
i
dy 39d!y Y¥SLNa90
HH |
ELECTRICAL CODE (NEC), ALL MANUFACTURER'S LISTING AND SYSTEM DETAILS
INSTALLATION INSTRUCTIONS, AND THE RELEVANT CODES AS
SPECIFIED BY THE AUTHORITY HAVING JURISDICTION'S (AHJ)
we
88'-8't DRIVEWAY | ‘44° VICINITY MA -
32.190 KW DC-(STC) / 23.000 KW AC
(74) HYUNDAI HIN-T435NF(BK)
fe 2] (2) TESLA 1707000-XX-Y
APPLICABLE CODES. 87'-1 4" j (29) TESLA MCI-2 RSD'S HIGH CURRENT
1.1.2 THE UTILITY INTERCONNECTION APPLICATION MUST BE ce i
APPROVED AND THE PV & ENERGY STORAGE SYSTEM MUST BE
INSPECTED PRIOR TO OPERATION
1.1.3 ALL PV & ENERGY STORAGE SYSTEM COMPONENTS;
|
REVISIONS
MODULES, UTILITY-INTERACTIVE INVERTERS, BATTERIES, AND er? solr REV| DESCRIPTION [DATE
soy
as Tabs ceiente: F
SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED
ae PET
FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC AND
2
StS
OTHER GOVERNING CODES
1.1.4 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL
eet
BUILDING CODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV es on
x Sse rash
ois
eS
RESISTANT. ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS 508.6 —
SATELLITE MAP
¥ pal
i,
REQUIRED BY THE NEC AND AH.
SCOPE OF WORK
1.2.1 CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND Itis a violation of the law for any person, unless SHEET TITLE
acting under the direction of a licensed
SPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC & ENERGY
STORAGE SYSTEM. THE CONTRACTOR WILL BE RESPONSIBLE professional, to aiter an item in any way. If an COVER PAGE
FOR COLLECTION OF EXISTING ONSITE CONDITIONS TO DESIGN, item bearing the seal of a licensed professional
SPECIFY, AND INSTALL THE PITCHED ROOF-MOUNTED PV
DRAWN DATE| 9/9/2025
Taide
is altered, the altering licensed professional shall
SYSTEM AND ENERGY STORAGE SYSTEM DETAILED IN THIS
DRAWN BY VHN
Sead Pasbpie
DOCUMENT affix to their item their seal and the notation
“altered by” followed by their signature and the
SHEET NUMBER
/T> PROPERTY PLAN
N date of such alteration, and a specific
description of the alteration.
\ev-or) SCALE:1" = 40'-0" PV-01
Page 2
NOTES:
1. ROOF ACCESS POINT SHALL NOT BE PLAN VIEW TOTAL ROOF AREA: 3012.79 FT? LEGEND CONTRACTOR
LOCATED IN AREAS THAT REQUIRE THE TOTAL PV ARRAY AREA: 1553.94 FT?
PLACEMENT OF GROUND LADDERS OVER
OPENINGS SUCH AS WINDOWS OR DOORS,
TOTAL % OF ROOF COVERED BY PV: 51.58%
° 3b" | WlttA;
AND LOCATED AT STRONG POINTS OF ; Yt) FIRE SETBACKS |TEMPIRESOLAR
1
BUILDING CONSTRUCTION IN LOCATIONS
—~!
WHERE THE ACCESS POINT DOES NOT
— CONFLICT WITH OVERHEAD STRINGING LEGEND [_] =MECHANICAL VENT
OBSTRUCTIONS SUCH AS TREE LIMBS,
WIRES OR SIGNS. SOLAR STRING 1 - 12 MODULES O = FLUE / PLUMBING VENT EMPIRE SOLAR SOLUTIONS
Ceeeaee
2. STRUCTURES, PATIO COVERS, AND/OR SOLAR STRING 2 - 1 MODULES 2-8 JOHNES ST
ADDITIONS BUILT WITHOUT PERMITS TO BE ID SHUTDOWN DEVICE WBURGH, 12550
RESOLVED BY A SEPARATE PERMIT. SOLAR STRING 3 - 12 MODULES (I PER 3 MODULES) sNONE - (848) 728-2165
et NI, SOLAR STRING 4 - 1 MODULES LIC, NO, - WC-29806-H17
foe RY fag ing PV MODULES
a“ et La SOLAR STRING 5 - 12 MODULES
WH STILT V7], (sé) SOLAR STRING 6 - 10 MODULES JUNCTION BOX; SIZE DETERMINED IN FIELD
‘ bc we seranes/ ale
Zi SOLAR STRING 7 - 6 MODULES CONDUIT RUN; SURFACE MOUNTED (ACTUAL
@ ) alr CONDUIT RUNS TO BE DETERMINED IN FIELD)
ale} |a
Gp | 5G4
my} wo i
@) @ aE UTILITY METER (UNDERGROUND SERVICE)
At
AV FAIITFIITTIT eo
: @ lea Ys aap
LLL pape artis
<< MAIN SERVICE PANEL
_ — Consulting, eG @) y YY ) os) TESLA BACKUP GATEWAY 3
" nee York COA #0022571 @) (3) Z Z 51e O AC DISCONNECT
=i [alg Y Y > PROJECT NAME & ADDRESS
Signed 9/10/2025 al 12 be / THOMAS MILL
Expires 7/31/2027 @4) (3) | [a] [ete @) a7 —f CS) Soren ET 50 CENTER RIDGE RD,
3|QI fete © ByWy © EAST AURORA, NY 14052
63) ©)
WiAte
[e)
oO GY
toy
ley
>7
Ay,
oO
Ci)
(2) TESLA 1707000-XX-Y
125A ESS COMBINER PANEL
.
APN #: 142489A187020000201 7000
2) WG GG Qe ky ©| @| ©| © T AHJ: TOWN OF AURORA
Y Y Pera ) O UTILITY: NEW YORK STATE
6e
{e) ATs : Vv
ELECTRIC & GAS
«: “AE spe) ) Yj ©|© Cc SYSTEM DETAILS
@]a1/9 Yi
ff fg YNBUAS Bld 81 S/F 32.190 KW DC-(STC) / 23.000 KW AC
@3) 3|w 7, : 7 WN (74) HYUNDAI HIN-T435NF(BK)
O} my] @) LLLL LL © FIRE SETINCK Y/Y YU (2) TESLA 1707000-XX-Y
me @) Y m (29) TESLA MCI-2 RSD'S HIGH CURRENT
score
Sie Y SLOPE =3
ot af pe,
Ga Ui
GAZ nO lSowoste sant REVISIONS
4 «3 Ni /) AY SLOPE =2
al =
© 2 © e7Ty
Rogss coro oa
AZIMUTH -270
REV] DESCRIPTION [DATE
AE
aie AY COMPOSITE SHINGLE
atZ] @&)
ZYAf mom
AZIM tk
- 270°
_ 25) O85 8 bo
CuIGIIOMe Y,
Y
ce eae a COMPOSITE SHINGLE
q VP IIITTTSIIT77, SLOPE = 24°
VACA 7, 36" FIRE SETBACK Y AZIMUTH ~90
Itis a violation of the law for any person, unless t Soran Li © @) Y RG Jaren 2x6" @ 20" 000.
F " ‘ . COMPOSITE SHINGLE
acting under the direction of a licensed Y OnE SF
professional, to alter an item in any way: If an Y —p| 44.6" |x ROOFS Sooitesy SHEET TITLE
item bearing the seal of a licensed professional SS Yj COMPOSITE SHINGLE N
is altered, the altering licensed professional shall 4 Y) Sed os SITE PLA
affix to their item their seal and the notation SS RAFTER - 2X6" @ 24° 0.0.
‘
altered by” +? followed by theirSe signature
et
and the COMPOSITE SHINGLE
so == DRAWN DATE 9/9/2025
date of such alteration, and a specific seaenincomcoit “a”
description of the alteration. 67.8" RP |RACTER- 2K B26 CS. DRAWN BY VHN
SLOPE ~ 24°
N (1 SITE P LAN cause MODULE
couros GTY
ae G “12
a SHEET V NUMBER
02
PV-02 SCALE:1" = 10'-0" AZIMUTH - 180° fo =
COMPOSITE SHINGLE
Page 3
DISTRIBUTED LOAD CALCULATIONS NOTE: = |
MODULE HYUNDAT HIN-T435NF(BK) 1. CONTRACTOR/INSTALLER TO VERIFY COMPATIBILITY OF LEGEND CONTRACTOR
MODULE WEIGHT 50.01 LBS ANY BRANDS OR PRODUCTS SUBSTITUTED OR USED AS
MODULE DIMENSIONS (L" x W') 67.8" x 44.6" ALTERNATES WITHIN ANY BRAND-SPECIFIC SYSTEMS. & - ATTACHMENT POINTS
TOTAL QTY, OF MODULES 74 CONTRACTOR SHALL SUPPLY AND PRESENT - RAIL SOLAR
TOTAL WEIGHT OF MODULES 3700.7 LBS CERTIFICATES OF COMPATIBILITY TO THE BUILDING iveviotation ul tke law tor sny nerenn:. unten! EMPIRE
TYEE OF RACKING K2 CROSSRAIL 44x OFFICIAL UPON INSPECTION AS NEEDED. 1 Heron, - STRUCTURAL MEMBER
TYPE OF ATTACHMENT K2 SPLICE FOOT XL acting under the direction of a licensed
DISTRIBUTED WEIGHT OF RACKING 10.5 PSF 2. REFER TO PV MODULE MANUFACTURER'S INSTALLATION professional, to alter an item in any way. If an
TOTAL WEIGHT OF ARRAY 4477.7 LBS INSTRUCTIONS FOR RAIL SPACING SPECIFICATIONS item bearing the seal of a licensed professional EMPIRE SOLAR SOLUTIONS
AREA OF MODULE aie Ser is altered, the altering licensed professional shall
TOTAL ARRAY AREA 1553.9 SQFT. fio Their hen the (and th ‘ 2-8 JOHNES ST
DISTRIBUTED LOAD 29 PSF affix to their item their seal and the notation NEWBURGH,12550
“altered by” followed by their signature and the PHONE - (845) 728-2165
date of such alteration, and a specific LIC. NO. - WC-29806-H17
description of the alteration.
4-0" OC ATTACHMENT SPACING CT] 4'-0" OC ATTACHMENT SPACING
@
|
-—
e| @
@
€
-@18
@
|S.
-
cs)
d
®
@
76 N. Meadowbrook Drive, Alpine UT
»
)
@
@
~—.
New York COA #0022571
rN
bd
.
?
A,
ad
a Lh.
ad
PROJECT NAME & ADDRESS
Signed 9/10/2025 THOMAS MILLER
4
«
+@
~~
f Expires 7/31/2027 f 50 CENTER RIDGE RD,
EAST AURORA, NY 14052
L strUCTURAL MEMBER @ 24" OC L_eyaucTuRE MEMBER @ 24" OC
(1.0)
PV-03
TYPICAL ATTACHMENT PLAN (PORTRAIT) (A.1\__ TYPICAL ATTACHMENT PLAN (LANDSCAPE) APN #: 142489A1870200002017000
AHJ: TOWN OF AURORA
SCALE: NTS PV-03 SCALE: NTS UTILITY: NEW YORK STATE
ELECTRIC & GAS
SYSTEM DETAILS
32.190 KW DC-(STC) / 23.000 KW AC
(74) HYUNDAI HIN-T435NF(BK)
(2) TESLA 1707000-XX-Y
(29) TESLA MCI-2 RSD'S HIGH CURRENT
NOTE: 6" MAXIMUM DISTANCE FROM ROOF SURFACE TO TOP OF PV MODULES
K2 END/MID CLAMP
REVISIONS
PV MODULE
EVEREST CROSS RAIL REV| DESCRIPTION [DATE
SEE ENLARGED VIEW PV MODULE 44-X RAIL
K2 SPLICE FOOT XL
K2 EVERSEAL FLASHING
MIN. (2) #14 SPLICE FOOT LAG
SCREWS INTO STRUCTURAL
MEMBER AS SPECIFIED BY
MANUFACTURER SHEET TITLE
(E) STRUCTURAL MEMBER
ATTACHMENT PLAN
(E) STRUCTURAL MEMBER & DETAILS
DRAWN DATE] — 9/9/2025
DRAWN BY VHN
SHEET NUMBER
(2_ ATTACHMENT DETAIL /3\ ENLARGED VIEW
\pv-03/ Scale: NTS \pv-03/ Scale: NTS
PV-03
Page 4
INVERTER SPECIFICATIONS SOLAR MODULE SPECIFICATIONS AMBIENT TEMPERATURE SPECIFICATIONS
MANUFACTURER/MODEL# _ |TESLA 1707000-XX-Y MANUFACTURER / MODEL # [HYUNDAI HIN-T435NF(BK) CONTRACTOR
RECORD LOW TEMP -20°C
POWER RATING 11500W VMP 32.1V
MAX CONT. OUTPUT CURRENT |48A IMP 13.56 A AMBIENT TEMP (HIGH TEMP 2% AVG.) 30 °C
MAX CURRENT PER MPPT (IMP) 115A VOC 38.6V MINIMUM CONDUIT HEIGHT ABOVE ROOF SURFACE |7/8"
MAX DC VOLTAGE 600V ISC 14.320 |_JEMPIRESOLAR
MAX SHORT CIRCUIT CURRENT |. TEMP. COEFF. Voc 0.25 GC
PER MPPT (ISC) 19A
EMPIRE SOLAR SOLUTIONS
2-8 JOHNES ST
METER#: 300 487 880 NEWBURGH, 12550
TO UTILITY GRID PHONE - (845) 728-2165
HYUNDAI HIN-T435NF(BK)
r
iH L2N
LIC. NO. - WC-29806-H17
LINE
I (E) BI-DIRECTIONAL
UTILITY METER
l 41-PHASE, 3-W,
| “9
LOAD 120V/240V
I
1 4
ia
F; (N) JUNCTION BOX
Sena A SUA NS (ay
I 600 V, NEMA 3R (N) TESLA BACKUP GATEWAY 3
{ ULLISTED ; 13, ' N) AC DISCON
a: 240V (N) PV PRODUCTION : VISIBLE LOCKABLE,
| a a METECOLISTED
NEAR LABELED D AND NON-FUSIBLE,
i Denk WIERNAL
aun NTERNAL
1 Ac
200A RATED
240V, NEMA 3R, UL LISTED
Ev rapt
LenaP
tj oro ci 1 LA L1 L4
I seed L2 \ 12 ia 12 I
I Gq PV 60A/2P| N N N N
i Te. (e} G
ig 4
if | aaa = © PV ST.
B0A/2P 4 2] L1_ 4 4 2008
an | (8) AKER
150a/2P MAIN
1 4 | ant 3_] M) tues a BONDED
F | METAL CONDUIT REQUIRED ENERGY uta - = as |e 2
t {| FOR DC CONDUCTORS STORAGE x GEC
pe | | THAT ARE RAN INTERIOR N LOAD i
1 3 | OF BUILDING
tig |
a L__| b, = EXISTING GROUNDING
1 4 il ELECTRODE SYSTEM PROJECT NAME & ADDRESS
bs =f slain agi aeesiaeaon | THOMAS MILLER
TESLA MCI - INLINE RAPID
SHUTDOWN DEVICE,
1 FOR EVERY 3 MODULES 50 CENTER RIDGE RD,
IN (&) 1500/2P MAIN
HYUNDAI HIN-T435NF(BK) BREAKER EAST AURORA, NY 14052
|
n tb
eer
itis a violation of the law for any person, unless
APN #: 142489A187020000201 7000
AHJ: TOWN OF AURORA
(E) 150A MAIN SERVICE
acting under the direction of a ticensed
(N) JUNCTION BOX PANEL 120/240V, 1-PHASE
(BACKUP PANEL) UTILITY: NEW YORK STATE
600 V, NEMA 3R (N) TESLA 1707000-XXx-Y professional, to alter an item in any way. If an ELECTRIC & GAS
=
UL LISTED 240V, 11kW, 13.5kWh
item bearing the seal of a licensed professional
SYSTEM DETAILS
ae
is altered, the altering licensed professional shall 32.190 KW DC-(STC) / 23.000 KW AC
affix to their item their seal and the notation (74) HYUNDAI HIN-T435NF(BK)
(2) TESLA 1707000-XX-Y
als
“altered by” followed by their signature and the
(29) TESLA MCI-2 RSD'S HIGH CURRENT
date of such alteration, and a specific
gees
description of the alteration.
L—--~--~--~=-—————~}|---~~--~ ad
TESLA MCI-2 HIGH METAL CONDUIT REQUIRED) ENERGY
CURRENT - INLINE RAPID FOR DC CONDUCTORS STORAGE REVISIONS
SHUTDOWN DEVICE, THAT ARE RAN INTERIOR
1 FOR EVERY 3 MODULES OF BUILDING
76 N. Meadowbrook Drive, Alpine UT REV| DESCRIPTION [DATE
New York COA #0022571 FULL HOME CONNECTION WILL BE DONE THROUGH LUGS
Signed 9/10/2025 BETWEEN METER AND MAIN SERVICE PANEL
Expires 7/31/2027
DESCRIPTION FORMULA RESULT
PV OVERCURRENT PROTECTION NEC 690.9(B) TOTAL INVERTER OUTPUT CURRENT x 1.25 = 96.0A x 1.25 120.00A (SELECTED OCPD = 125A) SHEET TITLE
DC WIRE CALCULATION
WIRE Ip [EXPECTED WIRE| TEMP DERATE| OTY CF CURRENT |CONDUIT FILL| MINIMUM CONDUIT eee CONDUCTOR — |CONDUCTOR AMPACITY| REQUIRED CIRCUIT ADJUSTED CONDUCTOR | NEUTRAL CONDUCTOR |GROUND WIRE SIZE SOB Aa L
TEMP (°C) (90 °C) CONDUCTORS DERATE | SIZE(TBD ON SITE) GE & TYPE! aMPACITY @ 90°C (A) @ 75°C (A) [CONDUCTOR AMPACITY (A)}_ AMPACITY @ 90 °C (A) SIZE & TYPE & TYPE
1 30 1 8 IN AIR N/A #10 AWG PV WIRE 40 35 22.38 40 NONE #6 AWG BARE Cu _| IDRAWN DATE 9/9/2025
2 30 1 8 0.7 3/4" METAL #10 THWN-2 40 35 22.38 28 NONE #8 THWN-2
1A 30 1 6 IN AIR N/A #10 AWG PV WIRE 40 35 22.38 40 NONE #6 AWG BARE Cu | DRAWN BY VHN
2A 30 1 6 0.8 3/4" METAL #10 THWN-2 40 35 22.38 32 NONE #8 THWN-2
AC WIRE CALCULATION SHEET NUMBER
3 30 1 g 1 3/4" #6 THWN-2 75 65 60 75 #6 THWN-2 #8 THWN-2
4 30 1 2 1 1-1/4" #1 THWN-2 145 130 125 145 #1 THWN-2 #6 THWN-2
5 30 1 2 1 1-1/2" #1/0 THWN-2 170 150 150 170 #110 THWN-2 #6 THWN-2 PV-04
8 30 1 2 1 1-1/4" #1/0 THWN-2 170 150 150 170 #110 THWN-2 NONE
Page 5
GENERAL NOTES CONTRACTOR
GROUNDING NOTES
SITE NOTES 2.5.1 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED INTERCONNECTION NOTES
2.7.1 LOAD SIDE INTERCONNECTION SHALL BE IN
|_JEMPIRESOLAR
2.1.1 ALADDER WILL BE IN PLACE FOR INSPECTION IN ACCORDANCE FOR THEIR PURPOSE, AND GROUNDING DEVICES EXPOSED TO
WITH OSHA REGULATIONS. THE ELEMENTS SHALL BE RATED FOR SUCH USE. ACCORDANCE WITH NEC 705.
2.1.2 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND 2.7.2 THE SUM OF THE UTILITY OCPD AND INVERTER
2.5.2 PV EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE EMPIRE SOLAR SOLUTIONS
THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH STORAGE CONTINUOUS OUTPUT MAY NOT EXCEED 120 PERCENT OF
WITH NEC 690 AND NEC TABLE 250.122.
BATTERIES. BUSBAR RATING PER NEC 705.
2.5.3 METAL PARTS OF MODULE FRAMES, MODULE RACKING, 2-8 JOHNES ST
2.1.3 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY 2.7.3 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) NEWBURGH, 12550
AND ENCLOSURES CONSIDERED GROUNDED IN ACCORDANCE
PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. WITH NEC 250. OUTPUT CIRCUIT CURRENT AND THE RATING OF THE PHONE - (845) 728-2165
2.1.4 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING 2.5.4 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL LIC. NO, - WC-29806-H17
AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED IN IN ACCORDANCE WITH NEC 690 AND INVERTER NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE
ACCORDANCE WITH SECTION NEC 110. BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE
MANUFACTURER'S INSTALLATION PRACTICES
2.1.5 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND 2.5.5 EACH MODULE WILL BE GROUNDED AS SHOWN IN LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY
MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVED SOURCE OCPD PER NEC 705.
MANUFACTURER DOCUMENTATION AND APPROVED BY THE
MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING AHJ. 2.7.4 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT
SERVES TO PROTECT THE BUILDING OR STRUCTURE. 2.5.6 THE GROUNDING CONNECTION TO A MODULE SHALL BE COMBINER PANEL, TOTAL RATING OF ALL OVERCURRENT
ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES PROTECTION DEVICES SHALL NOT EXCEED AMPACITY OF
EQUIPMENT LOCATIONS NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER BUSBAR. HOWEVER, THE MAIN OVERCURRENT PROTECTION
2.2.1 ALL EQUIPMENT SHALL MEET MINIMUM WORKING CLEARANCES IN MODULE. DEVICE MAY BE EXCLUDED IN ACCORDANCE WITH NEC 705.
ACCORDANCE WITH NEC 110. 2.5.7 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, 2.7.5 FEEDER TAP INTERCONNECTION (LOAD SIDE) IN
2.2.2 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE SHALL BE COLORED GREEN OR MARKED GREEN IF #4 AWG OR ACCORDANCE WITH NEC 705.
RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY LARGER PER NEC 250. 2.7.6 SUPPLY SIDE TAP INTERCONNECTION IN ACCORDANCE
2017 NATIONAL ELECTRICAL CODE. 2.5.8 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH WITH TO NEC 705 WITH SERVICE ENTRANCE CONDUCTORS
2.2.3 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV NEC 690 AND NEC 250. IF EXISTING SYSTEM IS INACCESSIBLE, IN ACCORDANCE WITH NEC 230.
2.7.7 BACKFEEDING BREAKER FOR ELECTRIC POWER PROJECT NAME & ADDRESS
MODULES IN ACCORDANCE WITH NEC 690. OR INADEQUATE, A GROUNDING ELECTRODE SYSTEM THOMAS MILLER
2.2.4 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PROVIDED IN ACCORDANCE WITH NEC 250, NEC 690 AND THE SOURCES OUTPUT IS EXEMPT FROM ADDITIONAL
50 CENTER RIDGE RD,
PERSONNEL IN ACCORDANCE WITH NEC APPLICABLE CODES. AHJ. FASTENING PER NEC 705.
EAST AURORA, NY 14052
2.2.5 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED 2.5.9 GROUND-FAULT DETECTION SHALL COMPLY WITH NEC 690
FOR OUTDOOR USAGE WHEN APPROPRIATE. TO REDUCE FIRE HAZARDS
APN #: 142489A187020000201 7000
STRUCTURAL NOTES DISCONNECTION AND OVERCURRENT PROTECTION NOTES AHJ: TOWN OF AURORA
2.3.1 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED IN UTILITY: NEW YORK STATE
2.6.1 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT
ACCORDANCE WITH THE CODE-COMPLIANT INSTALLATION MANUAL. ELECTRIC & GAS
WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING
TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED SYSTEM DETAILS
AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER 32.190 KW DC-(STC) / 23.000 KW AC
“LINE SIDE” (TYPICALLY THE UPPER TERMINALS). (74) HYUNDAI HIN-T435NF(BK)
EDGE OF THE ARRAY/SUB-ARRAY, INACCORDANCE WITH RAIL 2.6.2 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY (2) TESLA 1707000-XX-Y
MANUFACTURER'S INSTALLATION PRACTICES. PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH (29) TESLA MCI-2 RSD'S HIGH CURRENT
2.3.2 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S 2.6.3 PV SYSTEM CIRCUITS INSTALLED ON OR IN HABITABLE
SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION TO
& SEALED PER LOCAL REQUIREMENTS. REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN Nae sa
REVISIONS
2.3.3 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE
COMPLETED AND SEALED W/ APPROVED CHEMICAL SEALANT PER
ACCORDANCE WITH 690.
2.6.4 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING
Wyssling Consulting, PLLC REV| DESCRIPTION DATE
76 N. Meadowbrook Drive, Alpine UT
CODE BY ALICENSED CONTRACTOR. TO NEC 690 AND 240. New York COA #0022571
2.3.4 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO 2.6.5 INVERTER ON-GRID BRANCHES SHALL BE CONNECTED TO
GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING A SINGLE BREAKER OR GROUPED FUSE DISCONNECT(S) IN Signed 9/10/2025
MANUFACTURER OR PROFESSIONAL ENGINEERING GUIDANCE. ACCORDANCE WITH NEC 110. Expires 7/31/2027
itis a violation of the law for any person, unless
2.3.5 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL 2.6.6 IF REQUIRED BY THE AHJ, SYSTEM WILL INCLUDE
acting under the direction of a licensed
BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. ARC-FAULT CIRCUIT PROTECTION IN ACCORDANCE WITH NEC
690 AND UL1699B.
professional, to aiter an item in any way. If an SHEET TITLE
WIRING & CONDUIT NOTES item bearing the seal of a licensed professional
2.4.1 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR is altered, the altering licensed professional shall NOTES
THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON affix to their item their seal and the notation
“altered by” followed by their signature and the
MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT DRAWN DATE 9/9/2025
UP-SIZING. date of such alteration, and a specific
2.4.2 CONDUCTORS SIZED IN ACCORDANCE WITH THE NEC description of the alteration. DRAWN BY VHN
2.4.3 AC CONDUCTORS TO BE COLORED OR MARKED PER NEC
2.4.4 LISTED OR LABELED EQUIPMENT SHALL BE INSTALLED AND USED SHEET NUMBER
IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE LISTING
OR LABELING PER NEC PV-05
Page 6
>
} ne yy ning
a.
ELECTRICAL SHOCK HAZARD
|
ELECTRICAL SHOCK HAZARD [JEMPIRESOLAR
TERMINALS ON THE LINE AND e Sys
LABEL LOCATION: MAIN SERVICE DISCONNECT,
LOAD SIDES MAY BE ENERGIZED BGINT OF INTERCONNECTION TERMINALS ON BOTH LINE AND
L IN THE OPEN POSITION PER CODE: 705.12(B)(2)(3)(b) LOAD SIDES MAY BE ENERGIZED EMPIRE SOLAR SOLUTIONS
J IN THE OPEN POSITION
LABEL LOCATION: COMBINER PANEL, AC 2-8 JOHNES ST
DISCONNECT,
PER CODE: NECPOINT OF INTERCONNECTION
690.13(B DC VOLTAGE IS ALWAYS PRESENT WHEN NEWBURGH,12550
: : (B) MAIN PH OTOVOLTAIC [ SOLAR MODULES ARE EXPOSEDTO SUNLI GH a
PHONE - (845) 728-2165
LIC. NO, - WC-29806-H17
( Ray
A aca SYSTEM DISCONNECT LABEL LOCATION: DC DISCONNECT
AVVARNIN( LABEL LOCATION: MAIN SERVICE DISCONNECT, UTILITY METER PER CODE: NEC 690.13(B)
<A
ee
aea RTS PER CODE: NEC 690.13(B) ;
__ rn TION” Wyssling ‘Consulting, PLLC
RAPID SHUTDOWN SWITCH ee :: ANN A ha ibe ones 76 N. ae UT
TURN OFF PHOTOVOLTAIC AC
DISCONNECT PRIOR TO FOR SOLAR PV SYSTEM ae s : Sea Spe gil eos od
L EL LOCATION: MAIN SERVICE DISCONNECT :
WORKING INSIDE PANEL LABEL LOCATION: RSD INITI PER CODE: NEC 690.13(F), NEC 705.12(B)(3-4), NEC 690.59 Signed 9/10/2025
ATION DEVICE, AC DISCONNECT Expires 7/31/2027
LABEL LOCATION: COMBINER PANEL(S), MAIN SERVICE DISCONNECT PER CODE: NEC 690.56(C)(3)
PER CODE: NEC 110.27(C), OSHA 1910.145(f)(7) it is a violation of the law for any person, unless
acting under the direction of a licensed
professional, to alter an item in any way. If an
WARNING: PHOTOVOLTAIC item bearing the seal of a licensed professional
POWER SOURCE rs | as LABEL LOCATION: MAIN SERVICE DISCONNECT is altered, the altering licensed professional shall
LABEL LOCATION: DC CONDUIT/RACEWAY/CABLE TRAY PER CODE: NEC 705.12(B)(3-4), NEC 690.59 affixto thelr ttern thelr seal and the notation
PER CODE: NEC 690.31(G)(3-4) TURN RAPID SHUTDOWN
SWITCH TO THE “altered by” followed by their signature and the PROJE CT NAME & ADDRESS
"OFF" POSITION TO date of such alteration, and a specific THOMAS MILLER
SHUT DOWN PV SYSTEM deentitnn shies eetioe 50 CENTER RIDGE RD,
PHOTOVOLTAIC SYSTEM AC DISCONNECT
96.00 A
AND REDUCE
SHOCK HAZARD
‘ tas ai al :
s
EAST AURORA, NY 14052
RATED AC OUTPUT CURRENT: ALD IN THE ARRAY
NOMINAL OPERATING AC VOLTAGE: 240 V ( Al | lO N APN #: 142489A1870200002017000
LABEL LOCATION: POINT OF INTERCONNECTION LABEL LOCATION: MAIN SERVICE DISCONNECT AHJ: TOWN OF AURORA
PER CODE: NEC 690.54 PER CODE: NEC 690.56(C)(1)(a) UTILITY: NEW YORK STATE
MULTIPLE SOURCES OF POWER. ELECTRIC & GAS
SYSTEM DETAILS
sue RerST ITER " MAXIMUM SYSTEM VOLTAGE: 0 Ae FROM THE FOLLOWING SOURCES le (2) TESLA TOTO ea
LABEL LOCATION: AC Net - MAX RATED OUTPUT CURRENT OF THE CHARGE ADDRESS: 50 CENTER RIDGE RD, EAST AURORA, NY 14052
REVISIONS
_ CONTROLLER OR DC-TO-DC SOMERS. Mr Mest: Ea ADE
REV| DESCRIPTION [DATE
DO NOT DISCONNECT HAR LOCATION
LABEL L' INVERTER) DC DISCONNECT(S),
UNDER LOAD :
LABEL LOCATION: MAIN SERVICE DISCONNECT
PER CODE: NEC 690.15(C) & NEC 690.33(E)(2) .
3 | [| SHEET TITLE
LABEL LOCATION: MAIN SERVICE DISCONNECT WARNING LABELS
PER CODE: NEC 705.12(B)(3-4), NEC 690.59
DRAWN DATE 9/9/2025
MAIN SERVICE —N DRAWN BY VHN
PANEL |——— (2) TESLA 1707000-XX-Y
1] SHEET NUMBER
LABEL LOCATION: POINT OF INTERCONNECTION, COMBINER PANEL UTILITY METER 125K, Eos COMBINER. PANEL
PV PRODUCTION METER
PER GODE: NEG 708.12(8)2)(8)(¢) TESLA BACKUP GATEWAY 3 AC DISCONNECT PV-06
Page 7
CONTRACTOR
|_JEMPIRESOLAR
EMPIRE SOLAR SOLUTIONS
2-8 JOHNES ST
NEWBURGH, 12550
-— 5'-2"—
PHONE - (845) 728-2165
LIC. NO, - WC-29806-H17
— Ot."
—| : i —
14'-0"
“Ni areca
Wyssling Consulting, PLLC
76 N. Meadowbrook Drive, Alpine UT
New York COA #0022571
Signed 9/10/2025
4JSNOH AO LNOYS
ROOF 6
Expires 7/31/2027
—p-
PROJECT NAME & ADDRESS
THOMAS MILLER
50 CENTER RIDGE RD,
EAST AURORA, NY 14052
18'-4"
€ A00Y
APN #: 142489A187020000201 7000
-
>
8 SOO" AHJ: TOWN OF AURORA
UTILITY: NEW YORK STATE
| JOOY
ELECTRIC & GAS
»
SYSTEM DETAILS
32.190 KW DC-(STC) / 23.000 KW AC
(74) HYUNDAI HIN-T435NF (BK)
(2) TESLA 1707000-XX-Y
(29) TESLA MCI-2 RSD'S HIGH CURRENT
26'-8" REV|
REVISIONS
DESCRIPTION [DATE
13'-6"—49'.7"_
43/4"
ROOF 9
—
lt is a violation of the law for any person, unless
acting under the direction of a licensed
SHEET TITLE
professional, to alter an item in any way. If an INSTALLATION
itern bearing the seal of a licensed professional RESOURCE
is altered, the altering licensed professional shall
affix to their item their seal and the notation DRAWN DATE 9/9/2025
“altered by” followed by their signature and the
DRAWN BY VHN
date of such alteration, and a specific
description of the alteration. SHEET NUMBER
10
PV-07
**DIMENSIONS ARE 2D (FLAT)
Page 8
CONTRACTOR
H HYUNDAI eng. hd-hyundaies.co.kr |_TEMPIRESOLAR
ENERGY SOLUTIONS
Electrical Characteristics
HiN-TxxxNF(BK) HIN-T430NF(BK) HiN-T440NF(BK) EMPIRE SOLAR SOLUTIONS
HD HYUNDAI SOLAR MODULE : Open. circult
Short circuit current (isc)
2-8 JOHNES ST
NEWBURGH, 12550
PHONE - (845) 728-2165
Voltage at pmax (vmpp) 7
LIC. NO, - WC-29806-H17
NF(BK) Series Curr ant at Pmax (Impp)
Module efficiency
Power Class Sorting
Premium N-Type TOPCon Module Temperature coefficient of Pmax
HIN-T430NF(BK) | HIN-T435NF(BK) | HiN-T440NF(BK) Temperature coefficient of Vac
Temperature coefficient of sc
Bifaciality
~The ele: ti z 38 cor he 3 n*¢ % ri FE Hie .
Pmpp gain Pmpp[W] vmpp[vi tmppiA] Vac[V] IsclA]
7 5%
oe _ 458 —d
ener: AB
oa eee meee "38.80
1 pact Tt eae14.97
ea—_
28% $28 16.36 a 17.27
*Electrical character vith
Meshanesi ‘Charantaristics Installationisle Guide
Dimensions 1 722mm | x: 1,134mm{W)x 20mm (H) * Only qualified personnel should install or perform
ee Sin x 44,6in x 1,2in)
igi Se ee Re cs maintenance. PROJECT NAME & ADDRESS
‘ 7 + Be aware of dangerous high DC voltage.
THOMAS MILLER
Solar Cells N-Type TOPCon, 108 (6x18) monocrystalline 16BB haif-cut bifacial cells: , ee ee 50 CENTER RIDGE RD,
oe > Donot handle ar install modules when they are wet.
ae Cables EAST AURORA, NY 14052
Nominal Module Operation i
Temperature
| Front: 220mm(a, Bin) semise ‘cempered solar giaass with high transmittance Operating’ Temperature
and anti-reflective coating
2.0mim(O.
2 O8in) serni-tempered solar glass Maximum System Voltage DC 1, 500 ve APN #: 142489A187020000201 7000
| Anodized aluminum alloy Maximum ReverseCurrent 320A AHJ: TOWN OF AURORA
Maxiraum Test Load UTILITY: NEW YORK STATE
* on tar zat
Shipping Confi epatabians ELECTRIC & GAS
— Fire Performance
Vertical Packing pallet weight (kg)
SYSTEM DETAILS
40° Modules Per Pallet (pe 8) 32.190 KW DC-(STC) / 23.000 KW AG
28 _,_ Modules Per Container (pes) ‘ 936 (74) HYUNDAI HIN-T435NF(BK)
(2) TESLA 1707000-XX-Y
Module Diagram (unit: mm) 1-V Curves (HiN-T440NF(BK)) (29) TESLA MCI-2 RSD'S HIGH CURRENT
308temy Current [A]
7 BarcedeT ” 1.182004 . 7 16
ar ae “PET ; rt a ' ; ‘i
_———. —
f
we =
Z
ee nt
x
BOO
‘\ f
Pe
*
par
re = 2 REVISIONS
passa \ mt \ / \ sets \ let &
& 10
\ ait TORGon | | REV; DESCRIPTION (DATE
J) 4 \{ oe . | / ( aAca 8
TL) k 6
— Operating Cell Temp = 5°C
a NN x ; cece wf Nia. at Se it RA 4} — Operating Cell Temp = 25°C
= A-A 2 > Operating Cell Temp = 45°C
; 22.53% High-End Higher Long-Term Compatible For Residential
a 3 ~~ Operating Cell Temp = 65°C
High Efficiency TOPCon
eee oe 0
Bifaciality Reliability with Carport (Full Black Design) ; ES o 70 20
ier ea a pe
Technology Applications
i f gg » 7= Current [A]
‘ Vy 5 | 16
: 4 Ld t 4 E 4d
} af — Irradlance= 1,000W/m?
ty 4 Abele ie 12 \
HD Hyundai's Warranty Provisions @ HDHES TOPCon Module Certifi
tification ee
¢ 1
4i
1
i i ; a. a Bema
.
10} — Inradiance
= 800W/m?
Sx,
\\
ee re © PERC Standard —_—— ~
mick
cr
a ea Oa
i
|
LC
; | {
‘ta sc
l
k 1
(oc
Be
-
pen RANI
irradiance = GOOW/m?
\A
SHEET TITLE
cae es ar ‘ B- 6 —.\\\
+ 25-Year Product Warranty
* Materials and workmanshi
ansnip 89.4% 87.4% SB kiwa
PVEL
: |
~- _— easezeeoor
ze
BL a
4}
3
— Inradiance = 400W/m? \
~\
RESOURCE
* 30-Year Performance Warranty
= =
°
G
— irradiance = 200W/m?
10 20 30
\\
\ DOCUMENTS
FRONT SIDE REAR Voltage [v]
+ First year degradation: 1%
“Li arranty after initia! year: Q 5 1 1h 20 25 20 DRAWN DATE 9/9/2025
*Refer to HO LS stancero warranty
“or cletiuls. Sales & Marketing
[email protected]
HD Hyunda' Energy Suluons reserves the right te update or modify the
without prior notice. Always check the latest version of for ac
spe ‘onsand
i
din thi,
ing the preduct, FH
DAI DRAWN BY VHN
plzase refer to the Ir fl Over fand Warranty. fin the right of final interpretation. ENERGY SOLUTIONS
SHEET NUMBER
R-01
Page 9
CONTRACTOR
|TEMPIRESOLAR
EMPIRE SOLAR SOLUTIONS
Powerwall 3 Powerwall 3 Technical Specifications
Power Everything 2-8 JOHNES ST
NEWBURGH, 12550
System Technical Model Number 1707000-xx-y PHONE - (845) 728-2165
Specifications Nominal Grid Voltage (Input & Output) 120/240 VAC LIC. NO, - WC-29806-H17
Powerwall 3 is a fully integrated solar and battery system, designed to accelerate the transition to sustainable energy. Grid Type Split phase
Customers can receive whole home backup, cost savings, and energy independence by producing and consuming their
own energy while participating in grid services. Once installed, customers can manage their system using the Tesla App to FEM gs 60 He
customize system behavior to meat their energy goals. Nominal Battery Energy _ BSRWHACT
Nominal Output Power (AC) 5.8 kW 7.6 kW 10 kW 11.5 kW
Powerwall 3 achieves this by supporting up to 20 kW DC of solar and providing up to 11.5 kW AC of continuous power per Maximum Apparent Power 5,800 VA 7,600 VA 10,000 VA 11,500 VA
unit. It has the ability to start heavy loads rated up to 185 LRA, meaning a single unit can support the power needs of most
hornes. Powerwall 3 Expansions make it easier and more affordable to scale up customers’ systems to meet their current or
Maximum Continuous Current 2A SA ALTA 4BA
future needs. Powerwall 3 is designed for fast and efficient installations, modular system expansion, and simple connection to Overcurrent Protection Device? 30A 40A 60A 60A
any electrical service. Configurable Maximum Continuous Discharge 15.4 kW
Power Off-Grid (PV Only, -20°C to 25°C)
Maximum Continuous Charge Current / Power 20.8 A AC /5kW
(Powerwall 3 only)
Maximum Continuous Charge Current / Power 33.3A AC /8kW
(Powerwall 3 with up to (3) Expansion units)
Output Power Factor Rating A) -1(Grid Code configurable)
Maximum Output Fault Current (1s) 160A PROJECT NAME & ADDRESS
Maximum Short-Circuit Current Rating
THOMAS MILLER
1OkA
50 CENTER RIDGE RD,
Load Start Capability 185 LRA EAST AURORA, NY 14052
Solar to Battery to Home/Grid Efficiency
BK"
Solar to Home/Grid Efficiency 97.5%§
Power Scalability Up es 4 Pawerwall 3 units supported
APN #: 142489A187020000201 7000
AHJ: TOWN OF AURORA
Energy Scalability Up to 3 Expansion units (for a maximum total of 7 units)
UTILITY: NEW YORK STATE
Supported Islanding Devices Gateway 3, Backup Switch, Backup Gateway 2
ELECTRIC & GAS
Connectivity SYSTEM DETAILS
Hardware Interface Dry contact relay, Rapid Shutdown (RSD) certified switch 32.190 KW DC-(STC) / 23.000 KW AC
and 2-pin connector, RS-485 for meters (74) HYUNDAI HIN-T435NF(BK)
AC Metering Revenue Grade (+/- 0.5%, ANSI C12.20) (2) TESLA 1707000-XX-Y
(29) TESLA MCI-2 RSD'S HIGH CURRENT
Protections Integrated arc fault circuit interrupter (AFCI), Isolation
Monitor interrupter (IMI), PV Rapid Shutdown (RSD) using
Tesla Mid-Circuit interrupters
Customer Interface
Tesla Mobile App REVISIONS
Warranty 10 years
Values provided for 25°C (77°F), at beginning of life. 3.3 kW charge/discharge power. REV} DESCRIPTION DATE
2See Powerwall 3 Installation Manual for fuse requirements if using fuse for overcurrent protection.
315.4kW off-grid maximum continuous discharge power is only available if on-grid rating is 11.5 kW. If enabled, Powerwall 3
must be installed with an 80 A breaker and appropriately sized conductors.
‘Typical solar shifting use case.
5Tested using CEC weighted efficiency methodology.
’The customer Is expected to provide internet connectivity for Powerwall 3; cellular should not be used as the primary mode of
connectivity. Cellular connectivity subject to network operator service coverage and signal strength.
SHEET TITLE
RESOURCE
DOCUMENTS
2025 2025 Poworwali 3 Datashest
DRAWN DATE 9/9/2025
DRAWN BY VHN
SHEET NUMBER
R-02
Page 10
CONTRACTOR
{CIEMPIRESOLAR
EMPIRE SOLAR SOLUTIONS
Powerwall 3 Technical Specifications Powerwall 3 Technical Specifications
2-8 JOHNES ST
NEWBURGH,12550
PHONE - (845) 728-2165
Solar Technical Maximum Solar STC input
20 kW Mechanical Dimensions N1O5 x 609 x 193 mm (43.5 x 24 x 7.6 in)® LIC, NO, - WC-29806-H17
Specifications Withstand Voltage
. BOO VDE Specifications Total Weight of Installed Unit 182 kg (291.2 Ib)
PV DC input Voltage Range 80 — 550 VDC _ Weight of Powerwall 3 124 kg (272.5
Ib)
PV DC MPPT Voltage Range 80 — 480 VDC Weight of Glass Front Cover 6.5kg (14.5 Ib)
MPPTs 6
Weightof Wall Bracket 1.9 kg (4.2 Ib)
Maximum
Current per MPPT a (,.) At Mounting Options Floor or wall mount
Maximum Short Circuit Current
per MPPT (1,) 19 As ™These dimensions include the glass front cover being installed on Powerwall 3,
7Only applicable to Powerwall 3 units with 15 A I,,, on the product label. Otherwise, Powerwall 3 has an|.,,, of 13 A.
®When PV strings are combined on the roof and the DC input current exceeds the MPPT rating, a jumper can be used to
combine two MPPs into a single input to intake DC current up to 30 A hyp / 38 Al,, (or 26 A hyp / 30 Al, if Powerwall 3 is
labeled with
13 A |,,/ 15 AL sc)
Environmental Operating Temperature _ T2ONS to 50°C (-4PF to 12°F)?
Specifications f0100%, condensing PROJECT NAME & ADDRESS
Storage Temperature ~20°C to 30°C (-4°F to 86°F), up to 95% RH, non- TiOS mm THOMAS MILLER
condensing, State of Energy (SOE): 25% initial 50 CENTER RIDGE RD,
Maximum Elevation 3000 m (9843 ft) EAST AURORA, NY 14052
Environment
Indoor and outdoor rated
Enclosure Rating NEMA 3R
Ingress Rating P67 (Battery & Power Electronics) APN #: 142489A187020000201 7000
IPSS (Wiring Compartment) on i [—7 7 & AHJ: TOWN OF AURORA
Pollution Rating OB. UTILITY: NEW YORK STATE
Operating Noise @ 1m < 50 db(A) typical
< 62 db(A) maximum
}«—— 609 mm———>|
r 193
mm ELECTRIC & GAS
®Performance may be de-rated at operating temperatures above 40°C (104°F). SYSTEM DETAILS
32.190 KW DC-(STG) / 23.000 KW AG
(74) HYUNDAI HIN-T435NF(BK)
(2) TESLA 1707000-XX-Y
(29) TESLA MCI-2 RSD'S HIGH CURRENT
Compliance Certifications UL 1741, UL 9540, UL 95404, UL 3741, UL 1741 PCS,
UL 1741 SA, UL 1741 SB, UL 1741 Multimode, UL 1973,
Information UL 16998, UL 1998, CSA C22.2 No. 0.8, CSA C22.2 No.
1071, CSA C22.2 No, 330, CSA 22.3 No. 9, IEEE 1547, IEEE REVISIONS
15474, IEEE 1547.1, CA Rule No.21
REV| DESCRIPTION (DATE
United States ancl Canada
Emissions FCC Part 15 Class B, ICES 003
Environmental
RoHS Directive 2071/65/EU
Seismic AC156, IEEE 693-2005 (high)
Fire Testing Meets the unit level performance criteria of UL 9540A —
SHEET TITLE
RESOURCE
DOCUMENTS
DRAWN DATE 9/9/2025
2025 Powerwall 3 Datasheet 2025 Powerwatl 3 Datasheet
DRAWN BY VHN
SHEET NUMBER
R-03
Page 11
CONTRACTOR
[JEMPIRESOLAR
We support PV systems We support PV systems
Formerly Everest Solar Systems Formerly Everest Solar Systems @- EMPIRE SOLAR SOLUTIONS
x 2x 2-8 JOHNES ST
an ja] NEWBURGH, 12550
or “ — PHONE - (845) 728-2165
Units: [in] mm | LIC. NO, - WC-29806-H17
\ 98) \
Lo Lag]
4,50
Ln 13,50, wl
4K | 88.90
59). vg
Le. i
+O fo)
4.001
i ae in © jio1.60
a 141) |
S p li ce Foot XL fo 3]ry PROJECTTHOMAS & ADDRESS
NAME MILLER
Patent CPending | ex. 50 CENTER RIDGE RD,
[24 EAST AURORA, NY 14052
Wo
IECHNICAL SHEET
rw bese | ~ mel gre
i APN #: 142489A1870200002017000
ap a = AHJ: TOWN OF AURORA
{tem Number) Description Part Number ¢ E| [| UTILITY: NEW YORK STATE
= & ® ELECTRIC & GAS
a1 Splice
ae Foot XL 4000162 | | SpliceSplice Fo t Foot XLXL Kit,Kit, MillMi a 8S SYSTEM DETAILS
H 32.190 KW DC-(STC) / 23.000 KW AC
2
Hoke | Ke FlexFlash
,
Buty! i (74) HYUNDAI HIN-T435NF(BK)
(2) TESLA 1707000-XX-Y
tod (29) TESLA MCI-2 RSD'S HIGH CURRENT
3 MS x 60 lag screws
4 T-Bolt & Hex Nut Set | x
5 § A REVISIONS
Technical Data
REV| DESCRIPTION [DATE
Roof Type Composition shingle
Material Aluminum with stainless steel hardware | |
r
Finish Mill
|| a SHEET TITLE
“Roof Connection M5 x 60 lag screws S)
5 7 RESOURCE
Code Compliance UL 2703 | DOCUMENTS
ae CrossRail 44-X, 48-X, 48-XL, 80 DRAWN DATE 9/9/2025
Compatibility
k2-systems.com DRAWN BY VHN
ke-systems.com
SHEET NUMBER