NOT FOR CONSTRUCTION
  300 Pearl Street, Suite 130
  Buffalo, NY 14202
  716-551-6281
  labellapc.com

  EXP:  EXP:

  CERTIFICATE OF AUTHORIZATION NUMBER:
  PROFESSIONAL ENGINEERING: 0021272
  LAND SURVEYING: 0021271
  GEOLOGICAL: 0021659

  It is a violation of New York Education Law Art. 145 Sec. 7209 & Art. 147
  Sec. 7307, for any person, unless acting under the direction of a licensed
  architect, professional engineer, or land surveyor, to alter an item in any
  way. If an item bearing the seal of an architect, engineer, or land surveyor
  is altered; the altering architect, engineer, or land surveyor shall affix to
  the item their seal and notation "altered by" followed by their signature and
  date of such alteration, and a specific description of the alteration.

  © 2024
  2026 LaBella Associates

  HOME LEASING
  75 S CLINTON AVE SUITE 700,
  ROCHESTER, NEW YORK 14604

  WEST SENECA APARTMENTS
  2544 CLINTON ST,
  WEST SENECA, NY 14224

  FURNISH AND INSTALL IN LINE FUSES.
  BUSSMAN "TRON" WEATHERPROOF FUSES  NO:  DATE:  DESCRIPTION:
  \\cash.lab\u\Projects\Home Leasing Services\2241067 - Affordable Housing West Seneca\06_Drawings\Civil\C500 CONSTRUCTION DETAILS.dwg

  GASKETED HAND HOLE  HOLDERS #HEB-AD WITH "LP-CC" TIME DELAY  Revisions
  FUSES FOR EACH LUMINAIRE

  VARIES - CONCRETE BASE TO BE INSTALLED FLUSH WITH  PROJECT NUMBER:

  3  PARKING LOT STEEL POLE (MC-01 POLE)  FINISHED GRADE OR UP TO 36" EXPOSED. REFER TO SITE
  LIGHTING SUMMARY ON UTILITY PLAN(S)
  2241067
  C508  N.T.S.  36"  DRAWN BY:
  MAX  EMM / SCB
  FINISHED GRADE  REVIEWED BY:
  SRV / DPB
  GALVANIZED STEEL 'J' BOLTS (TYP. OF 4)  ISSUED FOR:
  3" MIN  SITE PLAN APPROVAL
  COVER
  1" PVC SCHEDULE 80 CONDUIT  DATE:
  24" MIN
  (TYP. OF 2)  4/20/2026
  66" MIN
  DRAWING NAME:
  #6 CU GROUND WIRE  3/4" PVC SCHEDULE 80 CONDUIT FOR GROUND
  ROD. CONNECTION AS REQUIRED.
  EXOTHERMIC WELD

  6#6 VERTICAL RODS AND
  #3 TIES @ 12" O.C.

  1/2"Øx8' CU DRIVEN
  24"Ø  CONSTRUCTION DETAILS
  GROUND ROD.
  PVC CONDUIT FITTING

  DRAWING NUMBER:

  2  TYPICAL SITE LIGHTING POLE BASE DETAIL  1  LIGHTING FIXTURES / PHOTO METRICS
4/20/2026 1:17:42 PM

  C508  N.T.S.  C508  N.T.S.

  C508