NOT FOR CONSTRUCTION
  COVER PIPE CONNECTION TO END  INSTALL FLAMP ON 24" (600 mm) ACCESS PIPE  OPTIONAL INSPECTION PORT
  CAP WITH ADS GEOSYNTHETICS 601T  PART #: MCFLAMP
  NON-WOVEN GEOTEXTILE
  MC-3500 CHAMBER
  MC-3500 END CAP
  6" MAX
  PONDING  4.0H
  MAX. PONDING/
  HEIGHT  1V
  RIM OF CB  OVERFLOW ELEV.  STORMTECH HIGHLY RECOMMENDS
  FLEXSTORM INSERTS IN ANY UPSTREAM  300 Pearl Street, Suite 130
  STRUCTURES WITH OPEN GRATES
  6" MIN. ORGANIC  Buffalo, NY 14202
  FILTER MEDIA  716-551-6281
  NOTES:  ELEVATED BYPASS MANIFOLD

  1.  CONTRACTOR SHALL INSTALL FILTER MEDIA AFTER SITE HAS BEEN STABILIZED TO  labellapc.com
  MINIMIZE POTENTIAL OF SEDIMENT CONTAMINATION OF MEDIA.
  2. FILTER MEDIA SHALL BE LOAM/SAND MIX, NYSDOT BIO SOIL MIX ITEM #208.01030022,
  CONTAINING A MINIMUM OF 85% TO 88% COARSE/MEDIUM SAND BY VOLUME, 8% TO 12%

  24" MIN.
  SOIL FINES, AND 3% TO 5% ORGANIC MATTER.
  FILTER MEDIA  3. ORGANIC FILTER MEDIA SHALL MEET SAME CRITERIA AS ABOVE WITH THE EXCEPTION OF
  CONTAINING 10% TO 12% ORGANIC MATTER.
  4. SOIL SHOULD FALL WITHIN USCS TYPES SM OR ML WITH PERMEABILITY OF AT LEAST 1.0
  FEET PER DAY. SOIL SHOULD BE FREE FROM STONES, STUMPS, ROOTS OR OTHER WOODY  SUMP DEPTH TBD BY  CATCH BASIN
  MATERIAL OVER 1" IN DIAMETER.  SITE DESIGN ENGINEER  OR MANHOLE
  (24" [600 mm] MIN RECOMMENDED)
  5. PLACEMENT OF THE PLANTING SOIL SHOULD BE IN LIFTS OF 12" TO 18", LOOSELY
  24" (600 mm) HDPE ACCESS PIPE REQUIRED  ONE LAYER OF ADSPLUS125 WOVEN GEOTEXTILE BETWEEN
  6"-12" DRAINAGE  COMPACTED TO AT MOST 80% PROCTOR TEST. PH RANGE: 5.2 - 7.00.  USE FACTORY PARTIAL CUT END CAP PART #:  FOUNDATION STONE AND CHAMBERS
  GRAVEL JACKET  6. FILTER FABRIC TO BE NON-WOVEN CLASS 'C', MIRAFI 180-N OR APPROVED EQUIVALENT  MC3500IEPP24BC OR MC3500IEPP24BW  8.25' (2.51 m) MIN WIDE CONTINUOUS FABRIC WITHOUT SEAMS
  7. DRAINAGE GRAVEL TO MEET AASHTO M-43. NO.67, SIZE 0.25" TO 0.75"
  8. CONTRACTOR TO PROVIDE PLANTING SOIL SUBMITTAL SPECIFICATION FOR REVIEW AND

  FILTER FABRIC
  APPROVAL PRIOR TO CONSTRUCTION.
  9. WETLAND SEED MIX SHALL BE USED AS INDICATED IN SPECIFICATIONS.  7  MC-3500 ISOLATOR ROW PLUS DETAIL  EXP:  EXP:
  4" PERFORATED PVC @ 0.2%  SUBGRADE OR
  10. CONTRACTOR SHALL PROVIDE AT LEAST TWO PERMEABILITY TESTS FOR EACH FACILITY  C504  N.T.S.
  EXISTING SOIL  DRAINAGE GRAVEL
  LOCATED AT OPPOSITE SIDES OF FACILITY.

  8  BIORETENTION  INSERTA TEE DETAIL  UNDERDRAIN DETAIL  CERTIFICATE OF AUTHORIZATION NUMBER:
  PROFESSIONAL ENGINEERING: 0021272
  NTS  NTS
  C504  N.T.S.  DO NOT INSTALL  STORMTECH  STORMTECH  LAND SURVEYING: 0021271
  INSERTA-TEE AT  CHAMBERS  STORMTECH  CHAMBER  GEOLOGICAL: 0021659
  CHAMBER JOINTS  END CAP
  PROVIDE CAST IRON FRAME  PROVIDE CAST IRON CLEANOUT THREADED PLUG IP THD OR BRASS  A  OUTLET MANIFOLD
  AND COVER, SET FLUSH  SCREW PLUG (HS 67). PVC PLUGS NOT ALLOWED. PROVIDE 1"-3"  It is a violation of New York Education Law Art. 145 Sec. 7209 & Art. 147
  WITH FINISH GRADE  10"  CLEARANCE BETWEEN PLUG & UNDERSIDE OF COVER  CONVEYANCE PIPE  Sec. 7307, for any person, unless acting under the direction of a licensed
  MATERIAL MAY VARY  architect, professional engineer, or land surveyor, to alter an item in any
  GRADE  (PVC, HDPE, ETC.)
  FOUNDATION STONE  way. If an item bearing the seal of an architect, engineer, or land surveyor
  FINISH GRADE FOR UNPAVED AREAS  BENEATH CHAMBERS  is altered; the altering architect, engineer, or land surveyor shall affix to
  the item their seal and notation "altered by" followed by their signature and
  7 1/2"

  WITHOUT FRAME AND COVER
  1"

  date of such alteration, and a specific description of the alteration.
  A
  ADS GEOSYNTHETICS 601T
  17"  INSERTA TEE  SECTION A-A
  CONNECTION
  INSERTA TEE TO BE  NON-WOVEN GEOTEXTILE  DUAL WALL  © 2024
  2026 LaBella Associates
  COMPACTED FILL TAMPED IN 6"  INSTALLED, CENTERED  PERFORATED
  (X)
  LAYERS  OVER CORRUGATION  HDPE
  STORMTECH  UNDERDRAIN
  STORM  SECTION A-A  SIDE VIEW  END CAP
  DWV PVC FEMALE ADAPTER, IP  PLACE ADSPLUS WOVEN GEOTEXTILE
  THREAD x SOCKET  (CENTERED ON INSERTA-TEE INLET) OVER
  C.O.
  BEDDING STONE FOR SCOUR PROTECTION AT
  6" RISER: SDR-35 PVC (ASTM D-2241)
  WITH SOLVENT WELDED JOINTS  LETTERING ON COVER
  SIDE INLET CONNECTIONS. GEOTEXTILE MUST
  EXTEND 6" (150 mm) PAST CHAMBER FOOT  CHAMBER
  MAX DIAMETER OF
  INSERTA TEE
  HEIGHT FROM BASE
  OF CHAMBER (X)
  B  B
  HOME LEASING
  FOUNDATION STONE
  PROVIDE SDR-35 GASKETED  NOTES:  SC-310  6" (150 mm)  4" (100 mm)
  A  BENEATH CHAMBERS
  75 S CLINTON AVE SUITE 700,
  FITTINGS AS NECESSARY; 1/8TH  SC-800  10" (250 mm)  4" (100 mm)  ROCHESTER, NEW YORK 14604
  6" x 6" x 6" SDR-35 TRUE 45 DEGREE  BEND, OR TWO 1/16TH BENDS  1. FRAME AND COVER TO BE USED  DC-780  10" (250 mm)  4" (100 mm)
  NOTES:
  ONLY IN PAVED AREAS.  ADS GEOSYNTHETICS 601T
  WYE WITH BENDS AS NECESSARY  COMPACTED CRUSHED STONE FILL  ·  PART NUMBERS WILL VARY BASED ON INLET PIPE  MC-3500  12" (300 mm)  6" (150 mm)
  A  NON-WOVEN GEOTEXTILE
  MATERIALS. CONTACT STORMTECH FOR MORE
  6" MIN.  6" MIN.  DEPTH = 1/2 OD + 12" MIN.  2. CRUSHED STONE: NO. 1 WASHED  MC-4500  12" (300 mm)  8" (200 mm)
  INFORMATION.
  STONE OR A MIX OF NO. 1 AND  ·  CONTACT ADS ENGINEERING SERVICES IF INSERTA TEE  MC-7200  12" (300 mm)  8" (200 mm)  NUMBER AND SIZE OF UNDERDRAINS PER SITE DESIGN ENGINEER
  4" (100 mm) TYP FOR SC-310 & SC-160LP SYSTEMS  SECTION B-B
  NO. 2 WASHED STONE  INLET MUST BE RAISED AS NOT ALL INVERTS ARE  INSERTA TEE FITTINGS AVAILABLE FOR SDR 26, SDR 35, SCH 40 IPS
  POSSIBLE.  6" (150 mm) TYP FOR SC-800, DC-780, MC-3500, MC-4500 & MC-7200 SYSTEMS
  RECOMMENDED METHODS FOR JOINING OF  GASKETED & SOLVENT WELD, N-12, HP STORM, C-900 OR DUCTILE IRON
  SOLVENT WELD PIPE:
  SELECT  SELECT
  GRANULAR
  FILL
  GRANULAR
  FILL
  1. CLEAN DRY HUBS & SPIGOTS
  5  MC-3500 INSERTA-TEE INLET  4  MC-3500 UNDERDRAIN
  2. APPLY PRIMER TO PARTS BEING  C504  N.T.S.  C504  N.T.S.
  CONNECTED

  3. APPLY PVC SOLVENT WELD CEMENT
  FLOW  DIRECTLY OVER PRIMER

  ** PVC TYPE IS COMPATIBLE FOR SOLVENT
  WELDING TO SDR-35 OR ANY OTHER PVC TYPE I  ACCEPTABLE FILL MATERIALS: STORMTECH MC-3500 CHAMBER SYSTEMS
  PIPE MADE TO STEEL PIPE OUTSIDE DIMENSIONS
  MATERIAL LOCATION  DESCRIPTION  AASHTO MATERIAL CLASSIFICATIONS  COMPACTION / DENSITY REQUIREMENT
  FINAL FILL: FILL MATERIAL FOR LAYER 'D' STARTS FROM THE
  6" SDR-35 PVC (ASTM D2241)  UNDISTURBED EARTH  CRUSHED STONE BEDDING  6" SDR-35 PVC (ASTM D2241)  PREPARE PER SITE DESIGN ENGINEER'S PLANS. PAVED
  TOP OF THE 'C' LAYER TO THE BOTTOM OF FLEXIBLE  ANY SOIL/ROCK MATERIALS, NATIVE SOILS, OR PER ENGINEER'S
  SERVICE LATERAL WITH PUSH ON  D  N/A  INSTALLATIONS MAY HAVE STRINGENT MATERIAL AND
  SERVICE LATERAL WITH PUSH ON  DEPTH=1/2 OD +6"  PAVEMENT OR UNPAVED FINISHED GRADE ABOVE. NOTE THAT  PLANS. CHECK PLANS FOR PAVEMENT SUBGRADE REQUIREMENTS.
  PREPARATION REQUIREMENTS.
  NEOPRENE RUBBER GASKETS  NEOPRENE RUBBER GASKETS  PAVEMENT SUBBASE MAY BE PART OF THE 'D' LAYER

  6  CLEANOUT FOR NEW STORM LATERAL  INITIAL FILL: FILL MATERIAL FOR LAYER 'C' STARTS FROM THE
  GRANULAR WELL-GRADED SOIL/AGGREGATE MIXTURES, <35%
  AASHTO M145¹
  A-1, A-2-4, A-3  BEGIN COMPACTIONS AFTER 18" (450 mm) OF MATERIAL OVER
  FINES OR PROCESSED AGGREGATE.  THE CHAMBERS IS REACHED. COMPACT ADDITIONAL LAYERS
  C504  N.T.S.  C
  TOP OF THE EMBEDMENT STONE ('B' LAYER) TO 18" (450 mm)
  ABOVE THE TOP OF THE CHAMBER. NOTE THAT PAVEMENT
  MOST PAVEMENT SUBBASE MATERIALS CAN BE USED IN LIEU OF
  OR  IN 12" (300 mm) MAX LIFTS TO A MIN. 95% PROCTOR DENSITY
  FOR WELL GRADED MATERIAL AND 95% RELATIVE DENSITY
  WEST SENECA APARTMENTS
  SUBBASE MAY BE A PART OF THE 'C' LAYER.  AASHTO M43¹
  THIS LAYER.
  3, 357, 4, 467, 5, 56, 57, 6, 67, 68, 7, 78, 8, 89, 9, 10
  FOR PROCESSED AGGREGATE MATERIALS.  2544 CLINTON ST,
  FRAME & GRATE: EJ CASTINGS  WEST SENECA, NY 14224
  NO. 4 BARS, 4  EMBEDMENT STONE: FILL SURROUNDING THE CHAMBERS
  RETICULINE GRATE, H-20 LOAD RATED,  CLEAN, CRUSHED, ANGULAR STONE OR RECYCLED CONCRETE5
  AASHTO M43¹
  GRASS  CONCRETE  B  FROM THE FOUNDATION STONE ('A' LAYER) TO THE 'C' LAYER  NO COMPACTION REQUIRED
  BICYCLE PROOF, ADA-COMPATIBLE  SIDES (TYP.)  3, 357, 4, 467, 5, 56, 57
  ABOVE.
  ASPHALT
  4,000 PSI CONCRETE POURED IN PLACE  FOUNDATION STONE: FILL BELOW CHAMBERS FROM THE  AASHTO M43¹
  CL  SUCH THAT RIM WILL MEET FINISH GRADE.  A  CLEAN, CRUSHED, ANGULAR STONE OR RECYCLED CONCRETE5  PLATE COMPACT OR ROLL TO ACHIEVE A FLAT SURFACE.2,3
  SUBGRADE UP TO THE FOOT (BOTTOM) OF THE CHAMBER.  3, 357, 4, 467, 5, 56, 57

  PLEASE NOTE:
  TOPSOIL  1. THE LISTED AASHTO DESIGNATIONS ARE FOR GRADATIONS ONLY. THE STONE MUST ALSO BE CLEAN, CRUSHED, ANGULAR. FOR EXAMPLE, A SPECIFICATION FOR #4 STONE WOULD STATE: "CLEAN, CRUSHED, ANGULAR NO. 4 (AASHTO M43) STONE".
  REFER TO ASPHALT  2. STORMTECH COMPACTION REQUIREMENTS ARE MET FOR 'A' LOCATION MATERIALS WHEN PLACED AND COMPACTED IN 9" (230 mm) (MAX) LIFTS USING TWO FULL COVERAGES WITH A VIBRATORY COMPACTOR.
  SOILTIGHT ADAPTER  PAVEMENT DETAILS  3. WHERE INFILTRATION SURFACES MAY BE COMPROMISED BY COMPACTION, FOR STANDARD DESIGN LOAD CONDITIONS, A FLAT SURFACE MAY BE ACHIEVED BY RAKING OR DRAGGING WITHOUT COMPACTION EQUIPMENT. FOR SPECIAL LOAD DESIGNS, CONTACT STORMTECH FOR
  4" MIN

  COMPACTION REQUIREMENTS.
  SELECT EARTH
  \\cash.lab\P\GLOBAL\Projects\Home Leasing Services\2241067 - Affordable Housing West Seneca\06_Drawings\Civil\C500 CONSTRUCTION DETAILS.dwg

  4. ONCE LAYER 'C' IS PLACED, ANY SOIL/MATERIAL CAN BE PLACED IN LAYER 'D' UP TO THE FINISHED GRADE. MOST PAVEMENT SUBBASE SOILS CAN BE USED TO REPLACE THE MATERIAL REQUIREMENTS OF LAYER 'C' OR 'D' AT THE SITE DESIGN ENGINEER'S DISCRETION.
  5. WHERE RECYCLED CONCRETE AGGREGATE IS USED IN LAYERS 'A' OR 'B' THE MATERIAL SHOULD ALSO MEET THE ACCEPTABILITY CRITERIA OUTLINED IN TECHNICAL NOTE 6.20 "RECYCLED CONCRETE STRUCTURAL BACKFILL".

  ADS GEOSYNTHETICS 601T NON-WOVEN GEOTEXTILE ALL  NO:  DATE:  DESCRIPTION:
  AROUND CLEAN, CRUSHED, ANGULAR STONE IN A & B LAYERS
  TYPE 1 OR 2 SUBBASE  PAVEMENT LAYER (DESIGNED  Revisions
  BY SITE DESIGN ENGINEER)
  2" DEEP x 2" WIDE
  XX" STANDARD H-20 GRATE  CONSTRUCTION JOINT  MINIMUM COVER ELEVATION: XX
  EXPOXY GROUT 100%  6"
  PLAN  SOLIDS (TYP.)  30" SQUARE
  TYP. ALL WALLS  D  *TO BOTTOM OF FLEXIBLE PAVEMENT. FOR UNPAVED
  8'
  PROJECT NUMBER:
  PERIMETER STONE
  C
  INSTALLATIONS WHERE RUTTING FROM VEHICLES MAY OCCUR,
  INCREASE COVER TO 24" (600 mm).  18" (450 mm)  (2.4 m)  2241067
  CONNECT UNDERDRAIN WHERE SHOWN  (SEE NOTE 4)  MIN*  MAX
  OR PROVIDE (2) 10 FOOT STUBS OF  12" (300 mm) MIN
  TOP CHAMBER ELEVATION: XX  DRAWN BY:
  PERFORATED PVC, OPPOSITE SIDES.  B
  100 YEAR PEAK ELEVATION: XX  EMM / SCB
  PRECAST SECTION ASTM C-478  EXCAVATION WALL
  (CAN BE SLOPED OR VERTICAL)
  REVIEWED BY:
  MEETING HS-20 LOADING  45"  10 YEAR PEAK ELEVATION: XX  SRV / DPB
  (1143 mm)
  XX" DRAIN BASIN  ISSUED FOR:
  SEE PLAN
  VARIES

  BASE CHAMBER ELEVATION: XX  SITE PLAN APPROVAL
  A  1 YEAR PEAK ELEVATION: 1069.54  BASE STONE ELEVATION: XX
  6" MIN.

  9" (230 mm) MIN  DATE:
  (SEE NOTE 3)  4/20/2026

  2.5' SEPARATION
  6" (150 mm) MIN
  SEE PLAN FOR DIAMETER  MC-3500  6"
  77" (1956 mm)  12" (300 mm) MIN
  END CAP  SUBGRADE SOILS  (150 mm) MIN  DRAWING NAME:
  (SEE NOTE 3)  **THIS CROSS SECTION DETAIL REPRESENTS
  MINIMUM REQUIREMENTS FOR INSTALLATION.
  GROUNDWATER ELEVATION: XX
  6" MIN. STONE BEDDING
  ALL CONCRETE
  NOTES:  PLEASE SEE THE LAYOUT SHEET(S) FOR
  TO LIMITS OF EXCAVATION.  PROJECT SPECIFIC REQUIREMENTS.
  TO BE 4,000 PSI  1.  CHAMBERS SHALL MEET THE REQUIREMENTS OF ASTM F2418, "STANDARD SPECIFICATION FOR POLYPROPYLENE (PP) CORRUGATED WALL STORMWATER COLLECTION CHAMBERS"
  SAME MATERIAL USED
  CHAMBER CLASSIFICATION 45x76 DESIGNATION SS.
  6" MIN.

  FOR SEWERS.
  SOILTIGHT ADAPTER  2.  MC-3500 CHAMBERS SHALL BE DESIGNED IN ACCORDANCE WITH ASTM F2787 "STANDARD PRACTICE FOR STRUCTURAL DESIGN OF THERMOPLASTIC CORRUGATED WALL STORMWATER COLLECTION CHAMBERS".

  NOTES:
  3.  THE SITE DESIGN ENGINEER IS RESPONSIBLE FOR ASSESSING THE BEARING RESISTANCE (ALLOWABLE BEARING CAPACITY) OF THE SUBGRADE SOILS AND THE DEPTH OF FOUNDATION STONE WITH CONSIDERATION
  FOR THE RANGE OF EXPECTED SOIL MOISTURE CONDITIONS. REFERENCE STORMTECH DESIGN MANUAL FOR BEARING CAPACITY GUIDANCE.
  CONSTRUCTION DETAILS
  6" STONE BASE

  4.  PERIMETER STONE MUST BE EXTENDED HORIZONTALLY TO THE EXCAVATION WALL FOR BOTH VERTICAL AND SLOPED EXCAVATION WALLS.
  1.  THE ENTIRE EXTERIOR & INTERIOR SURFACES OF THE CATCH BASIN SHALL BE PAINTED WITH TWO COATS OF  5.  REQUIREMENTS FOR HANDLING AND INSTALLATION:
  BITUMASTIC COATING.  ·  TO MAINTAIN THE WIDTH OF CHAMBERS DURING SHIPPING AND HANDLING, CHAMBERS SHALL HAVE INTEGRAL, INTERLOCKING STACKING LUGS.
  2.  CATCH BASIN SHALL NOT BE CONNECTED TO ANY SANITARY SEWER.  ·  TO ENSURE A SECURE JOINT DURING INSTALLATION AND BACKFILL, THE HEIGHT OF THE CHAMBER JOINT SHALL NOT BE LESS THAN 3” (75 mm).
  3.  PROVIDE FRAMES AND GRATES CONFORMING TO NYSDOT STANDARD SHEETS M655-10R3, M655-6.  ·  TO ENSURE THE INTEGRITY OF THE ARCH SHAPE DURING INSTALLATION, a) THE ARCH STIFFNESS CONSTANT AS DEFINED IN SECTION 6.2.8 OF ASTM F2418 SHALL BE GREATER THAN OR EQUAL TO 500 LBS/FT/%.
  SECTION  4.  FRAMES TO HAVE APPROPRIATE STRAP ANCHORS.  AND b) TO RESIST CHAMBER DEFORMATION DURING INSTALLATION AT ELEVATED TEMPERATURES (ABOVE 73° F / 23° C), CHAMBERS SHALL BE PRODUCED FROM REFLECTIVE GOLD OR YELLOW COLORS.
  DRAWING NUMBER:

  3  DRAIN BASIN  2  CATCH BASIN  1  MC-3500 CROSS SECTION
4/20/2026 1:17:45 PM

  C504  N.T.S.  C504  N.T.S.  C504  N.T.S.

  C504