Village of East Aurora, NY

  § 263-15  § 263-15

  WATER FOREMAN — The Water Foreman of the Public Works Department of the Village
  of East Aurora, or his/her authorized representative.
  WATER SUPERVISOR — The consumer, and/or owner of premises, and/or a person the
  premises charged with the responsibility of complete knowledge and understanding of the
  water supply piping within the premises and for maintaining the consumer's water system free
  from cross connections and other sanitary defects, as required by this chapter and all other
  required regulations and laws.
  C.  "Shall" is mandatory; "may" is permissive.
  D.  Protection required.
  (1) Where protection is required. The water system shall be required to maintain a degree of
  protection commensurate with the degree of hazard regardless of whether the hazard is
  immediate or potential. To that extent, the Cross Connection Manual published by
  NYSDOH shall be used as a guide to determine where protection is required. It shall be
  the responsibility of the water user to provide and maintain such required protection
  devices and such devices shall be of a type acceptable to the NYSDOH.
  (2) Type of protection. The type of protective device required shall depend on the degree of
  hazard as tabulated below:
  (a) At the service connection to any premises where there is an auxiliary water supply
  handled in a separate piping system with no known cross connection, the public
  water supply shall be protected by an approved reduced pressure zone device.
  (b) At the service connection to any premises on which a substance that would be
  objectionable, but not necessarily hazardous to health if introduced into the public
  water supply, is handled so as to constitute a cross connection, the public water
  supply shall be protected by an approved double check valve assembly.
  (c) At the service connection to any premises on which a substance of unusual toxic
  concentration or danger to health is or may be handled, but not under pressure, the
  public water supply shall be protected by an air gap separation or an approved
  reduced pressure zone backflow prevention device. If an air gap is installed, it shall
  be located as close as practical to the water meter, and all piping between the water
  meter and receiving tanks shall be entirely visible. A reduced pressure zone device
  when installed shall be located as close as possible to the property line.
  (d) At the service connection to any premises on which any material dangerous to
  health, or toxic substance and toxic concentration, is or may be handled under
  pressure, the public water supply shall be protected by an air gap separation. The
  air gap shall be located as close as practical to the water meter, and any piping
  between the water meter and receiving tanks shall be entirely visible. If these
  conditions cannot reasonably be met, the public water supply shall be protected
  with an approved reduced pressure zone backflow prevention device and it shall be
  located as close as possible to the property line.
  (e) At the service connection to any sewage treatment plant or sewage pumping

Downloaded from https://ecode360.com/EA0398 on 2026-03-04