Text · page 690 of 1174
Read the whole document on one page (all 1174 pages, each with its own heading)
ARM Hydrant Flow Test Inquiry -- Hydrant: J13E24 Test Date/Time: 7/25/2019 14:15 CHI095-B Address: 115 SLADE AVE Side: E Location: 2ND N/O RIDGE RD W SENECA Size of Main/Branch: 24"/6" Fire District: 68024 FIRE DIST 5 Water District: 044 ECWA AREA-WEST SENECA ¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯ Performed By: BPS/CHM Comments: HYDRANT FLOW TEST REQUESTED BY THOMAS YAGER, ISO PHONE: 716-207-4967; EMAIL: [email protected] CW #40336 ¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯ Dischrge Coef: .90 Elvtn Usgs(ft): Static(psi): 90 Residual(psi): 84 Required Residual Pressure(psi): 20 Gallons Used..: 7,140 Total Flow(gpm): 2,372 Flow at Reqd Resid Pressure: 8,939 Flow Hydrants: C Flow Hyd Flow Hydrant Address Main/Brnch Nzle Size Pitot Flow Comments J13 E16 OP 160 SLADE AVE 24"/6" 1: 2.50 50.0 1,186 3RD HYD N/O RIDGE RD 2: 2.50 50.0 1,186 3: Tot Flow: 2,372 ¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯ Bottom I=Flow Hydrant Inquiry ENTER=Continue F3=Exit F6=Maintain Test F7=Test Hydrant Inquiry F15=Print Test Information Page 690 of 1174