sections 7209N and 7301 of the New York State Education Law for any person, unless acting under the direction of a registered architect, licensed engineer or land surveyor
to alter this drawing. If altered such R.A., P.E. or L.L.S. shall affix his or her seal, signature, the date,the notation "Altered By" and a specific description of the alteration.
  GENERAL NOTES:  DRAWING KEYNOTES:  #
All Rights Reserved. Reuse of these documents without the expressed written permission of Carmina Wood Design is prohibited. WARNING it is a violation of article 145

  A.  REFER TO CIVIL PLANS FOR EXACT CONDUIT ROUTING AND PATHWAYS. SIZE OF CIRCUITRY  1.  DUAL PORT CHARGING STATION: PROVIDE LEVEL 2 CHARGER AND POWER FROM 40A-2P CIRCUIT
  AND EQUIPMENT AND DEVICE LOCATIONS ARE SHOWN ON THIS PLAN.  BREAKER IN PANEL LP-1 VIA 2#8 & 1#8G IN 2"C. CONDUIT SHALL BE SAND BED ENCASED.

  B.  ROUTING OF UNDERGROUND ELECTRIC IS DIAGRAMMATIC. FIELD COORDINATE EXACT  2.  PROVIDE 3/4"X10' GROUND ROD AND BOND TO GENERATOR GROUND BUS WITH #2/0 WIRE.
  ROUTING.
  3" CONDUITS  3.  PROVIDE GROUNDING GRID. REFER TO DETAIL '5' ON E-400 FOR ADDITIONAL REQUIREMENTS.
  C.  ALTHOUGH EVERY ATTEMPT HAS BEEN MADE TO INDICATE EXISTING UTILITIES AS
  A  A  S  4" CONDUITS  4" CONDUITS  ACCURATELY AS POSSIBLE FROM EXISTING SURVEYS, DRAWINGS AND OTHER DATA; OTHER  4.  FOR THE INDICATED FIXTURES, AS A PART OF BASE BID, PROVIDE EMPTY 1"C WITH PULLSTRING TO
  A  S
  UTILITIES MAY BE PRESENT OR PLACED IN DIFFERENT LOCATIONS. VERIFY EXACT LOCATION  EACH LOCATION FROM THE ELECTRIC ROOM. COORDINATE FINAL FIXTURE LOCATION WITH SITE  4
  OF EXISTING UTILITIES BY TEST HOLES AND/OR SITE INVESTIGATIONS. NOTIFY "DIG/SAFELY"  CONTRACTOR. AS A PART OF ALTERNATE BID #1, INSTALL THE INDICATED FIXTURES COMPLETE.
  A  A
  TO LOCATE ALL EXISTING UNDERGROUND UTILITIES PRIOR TO COMMENCEMENT OF SITE  CIRCUIT TO SITE LIGHTING CIRCUIT IN PANEL LP-1, 20A-2P CIRCUIT BREAKER; CIRCUIT NUMBER 27,29.
  WORK.
  5.  FOR THE INDICATED FIXTURES AS A PART OF BASE BID, EXTEND EMPTY CONDUIT WITH PULLSTRING AS
  D.  HAND EXCAVATE WHERE CROSSING EXISTING UNDERGROUND UTILITIES.  SHOWN AND ABANDON UNDERGROUND. AS A PART OF ALTERNATE #2, INSTALL THE INDICATED
  FIXTURES COMPLETE. CIRCUIT TO SITE LIGHTING CIRCUIT IN PANEL LP-1, 20A-2P CIRCUIT BREAKER;
  E.  FIELD VERIFY LOCATION OF NEW ELECTRICAL EQUIPMENT BEFORE INSTALLATION WITH  CIRCUIT NUMBER 20,22. EXTEND/REROUTE CIRCUITRY PROVIDED IN BASE BID POWERING FIXTURES
  OWNER.  INDICATED BY NOTE 6.
  GENERAL DETAIL NOTES:  GENERAL DETAIL NOTES:  F.  PROVIDE NYLON PULL CORD IN ALL SPARE CONDUITS FOR PULLING OF FUTURE CABLING.  6.  AS A PART OF BASE BID, INSTALL THE INDICATED FIXTURES COMPLETE. CIRCUIT TO SITE LIGHTING
  CIRCUIT IN PANEL LP-1 VIA 2#8 & 1#8G IN 1"C FROM 20A-2P CIRCUIT BREAKER; CIRCUIT NUMBER 20,22.
  • A = ACTIVE CONDUIT  • A = ACTIVE CONDUIT  GENERAL DETAIL NOTES:  G.  ALL EXCAVATION, BACKFILL, AND SITE RESTORATION SHALL BE PART OF THE ELECTRICAL
  • S = SPARE (EMPTY) CONDUIT  • S = SPARE (EMPTY) CONDUIT  WORK CONTRACT.  7.  REMOVE INDICATED POWER/LIGHT POLE. REMOVE ASSOCIATED OVERHEAD CONDUCTORS BACK TO
  EXISTING TO REMAIN POWER POLE. PROVIDE NEW SECONDARY CONDUCTORS UNDERGROUND FROM
  CONDUITS (ACTIVE AND SPARE) SHALL BE SAND BED ENCASED. REFER TO
  • A = ACTIVE CONDUIT  H.  SITE LIGHTING LOCATIONS ARE SHOWN FOR REFERENCE ONLY, COORDINATE FINAL  POLE MOUNTED TRANSFORMERS TO THE OUTBUILDINGS AS INDICATED ON THE DRAWINGS.
  CONDUITS (ACTIVE AND SPARE) SHALL BE SAND BED ENCASED. REFER TO
  DETAIL #3 ON E-400 FOR INSTALLATION REQUIREMENTS.  DETAIL #3 ON E-400 FOR INSTALLATION REQUIREMENTS.  LOCATIONS WITH SITE CONTRACTOR. PROVIDE CIRCUITRY AS CALLED AS NOTED.
  CONDUITS SHALL BE SAND BED ENCASED. REFER TO DETAIL #3 ON E-400 FOR  8.  PROVIDE NEW CONCRETE ENCASED DUCT BANK FROM EXISTING POLE WITH TRANSFORMERS TO
  INSTALLATION REQUIREMENTS.  EXISTING POLE WITH 300A MCB 208/120V PANEL MOUNTED TO IT. PROVIDE 2 PARALELLED SETS OF
  4#500 & #2G IN 3-1/2"C FROM EXISTING POLE MOUNTED TRANSFORMER TO POLE MOUNTED PANEL VIA
  NEW CONCRETE ENCASED DUCT BANK.

  SECONDARY FEEDER DUCTBANK SECTION  PRIMARY FEEDER DUCTBANK SECTION  TELECOM FEEDER DUCTBANK SECTION  9.  AS A PART OF BASE BID, INSTALL THE INDICATED FIXTURES COMPLETE. CIRCUIT TO SITE LIGHTING
  2  NTS
  3  NTS
  4  NTS
  CIRCUIT IN PANEL LP-1 VIA 2#8 & 1#8G IN 1"C FROM 20A-2P CIRCUIT BREAKER; CIRCUIT NUMBER 27,29.

  10.  PROVIDE POWER FOR SITE PUMP TANK FROM PANEL LP-1 VIA 2#3 & #3G IN 1-1/4"C FROM 15A-2P CIRCUIT
  BREAKER; CIRCUIT NUMBER AS INDICATED.

  11.  PROVIDE POWER FOR SITE GRINDER PUMP FROM PANEL LP-1 VIA 2#4 & #4G IN 1-1/4"C FROM 15A-2P
  CIRCUIT BREAKER; CIRCUIT NUMBER AS INDICATED.
  4

  Town of Hamburg Community Center
  EXISTING 1 STORY BUILDING

  1  2  3  4  5  6  7  8
  4
  A  1" CONDUIT

  CONDUITS:

  Hamburg, New York 14075
  GENERAL DETAIL NOTES:  1. 2"C FOR CONTROL WIRING FOR GENERATOR REMOTE ANNUNCIATOR PANEL.
  2. 1"C FOR ATS CONTROL WIRING.

  Bid/Permit Set
  • A = ACTIVE CONDUIT
  © Carmina Wood Design

  3. 1-1/4"C FOR ATS-OS EMERGENCY POWER FEEDER.

  2982 Lakeview Road
  CONDUITS SHALL BE SAND BED ENCASED. REFER TO  4. 1"C FOR ATS-LS EMERGENCY POWER FEEDER.
  DETAIL #3 ON E-400 FOR INSTALLATION REQUIREMENTS.  5. 1/2"C FOR GENERATOR BATTERY CHARGER. REFER TO DETAIL 3 ON E-300
  4  9
  FOR ADDITIONAL REQUIREMENTS.
  6. 1/2"C FOR GENERATOR BATTERY HEATER. REFER TO DETAIL 3 ON E-300 FOR
  ADDITIONAL REQUIREMENTS.
  7. 1/2"C FOR GENERATOR ALTERNATOR STRIP HEATER. REFER TO DETAIL 3 ON
  E-300 FOR ADDITIONAL REQUIREMENTS.
  LIGHT POLE FEEDER DUCTBANK SECTION  8. 1/2"C FOR GENERATOR BLOCK HEATER. REFER TO DETAIL 3 ON E-300 FOR
  5  NTS
  ADDITIONAL REQUIREMENTS.

  CONDUITS SHALL BE SAND BED ENCASED. REFER TO DETAIL #3 ON E-400 FOR

  02/05/2026
  03/18/2026
  04/14/2026
  08/24/2026
  INSTALLATION REQUIREMENTS.  EXISTING POWER
  POLE WITH POLE

  Date
  4  8 MOUNTED
  TRANSFORMERS
  SECONDARY FEEDER DUCTBANK SECTION  E-001
  6  NTS
  EXISTING POWER
  7  7
  POLE WITH POLE
  MOUNTED PANEL  EXISTING

  DO NOT
  1

  ENTER
  9  1  POWER POLE

  8

  No. Description
  2  9
  GENERAL NOTES:

  RFP #01

  RFP #05
  RFI-018
  CCD #1
  REVISIONS:
  4
  A.  ALL EQUIPMENT SUPPLIED BY ELECTRICAL CONTRACTOR  4
  2  SHALL BE APPROVED BY ENGINEER PRIOR TO PURCHASE.
  5  9
  11  11  11  6
  6  6

  1
  2
  3
  4
  10  3

  11
  4  4
  4
  KEYED NOTES:  X  STOP
  STOP

  1.  EXISTING POLE TO REMAIN.  4
  E-001
  2.  EXISTING TOP CROSS ARM TO REMAIN. PROVIDE LOWER
  6  CROSS ARMS TO SUPPORT HOOK SWITCH DISCONNECT.  5  6
  12  LOWER CROSS ARMS SHALL BE SAME DIMENSION AS TOP

  9 ft
  7  CROSS ARM.

  08/08/2025
  3.  PROVIDE HOOK STICK DISCONNECT, S&C SMD-20 OR
  APPROVED EQUAL. MAINTIAN CLEARANCE BETWEEN PHASES
  OF EXISTING OVERHEAD LINE.
  GYM

  4.  PROVIDE 5.1KV MCOV/40K DUTY CYCLE SURGE ARRESTOR.  5

  Sealed:
  MOUNT TO POLE.  E-001
  1
  13  9  9  9  5.  #2/0 GROUND WIRE DOWN LEAD FROM LIGHTNING ARRESTOR
  TO GROUND RODS.
  5
  6.  PROVIDE GROUND WIRE SLEEVE 15' AFG.  PROPOSED COMMUNITY CENTER  3
  20,050± SF
  4  F.F.E. = 768.40
  6  2  7.  PROVIDE #2/0 CONNECTION TO PIPE CLAMP ON BOTH ACTIVE
  & SPARE CONDUIT.
  10  6
  8.  5/8 X 8'-0" GROUND ROD WITH GROUND CLAMP.  11
  APPROXIMATE LOCATION OF
  9.  OVERHEAD CONDUCTORS, INSULATORS AND ASSOCIATED  ELECTRIC ROOM  4
  3  3  2  10
  10  HARDWARE.  E-001  DRAWING NAME:
  34,36
  4
  4
  10
  10.  CONDUCTORS FROM OVERHEAD TO CUSTOMER SERVICE
  TRANSFORMER VIA HOOK STICK SWITCHES.  6  2
  1
  SITE PLAN - ELEC
  E-001  E-001  1
  11.  WIRING TO LIGHTNING ARRESTOR.  10
  12
  12.  CABLE GROUND TO DOWN LEAD.  2  GENERATOR  26,28  30,32
  7'  33,35
  12  CUSTOMER
  13.  TWO 5"C; ONE ACTIVE & ONE SPARE.  BUILDING  OWNED
  3' MIN  3' MIN  8  3
  6  TRANSFORMER  POLE (E)
  5  E-001
  Date:  08/08/2025
  Drawn By:  SAS
  8  Checked By:  RPP
  DRAWING NO.
  CUSTOMER POLE DETAIL
  7  NTS

  SITE PLAN - ELEC
  E-001
  Project No: 24-6059
  1  1" = 40'-0"  169