GRADE

  6" TOPSOIL (MIN.)  FRAME AND GRATE SHALL BE NEENAH R-1792-FG OR R-1792-FL  FRAME AND GRATE SHALL BE NEENAH R-1792-FG OR R-1792-FL W/"STORM" CAST IN
sections 7209N and 7301 of the New York State Education Law for any person, unless acting under the direction of a registered architect, licensed engineer or land surveyor
to alter this drawing. If altered such R.A., P.E. or L.L.S. shall affix his or her seal, signature, the date,the notation "Altered By" and a specific description of the alteration.

  NOTE:TO BE USED IN  W/"STORM" CAST IN COVER IF SOLID COVER IS SPECIFIED, HEAVY COVER IF SOLID COVER IS SPECIFIED, HEAVY DUTY BICYCLE PROOF FRAME AND GRATE
All Rights Reserved. Reuse of these documents without the expressed written permission of CARMINAWOOD DESIGN is prohibited. WARNING it is a violation of article 145

  TRENCH WIDTH

  Greensboro
  NYSDOT RIGHT-OF-WAY  DUTY BICYCLE PROOF FRAME AND GRATE TO BE USED IN PARKING TO BE USED IN PARKING LOT AREAS UNLESS OTHERWISE SPECIFIED
  (I.D. + 24")  LOT AREAS UNLESS OTHERWISE SPECIFIED  8" DIA. INLINE YARD DRAIN WITH
  24" DIA.  "STANDARD" GRATE
  2  8"  STAND.  24" DIA.
  GRADE  STANDARD

  EXCAVATED FROM TRENCH
  BACKFILL WITH MATERIAL
  TRENCH WIDTH
  (I.D. + 24")
  RISER RINGS W/GASKET
  AS REQUIRED  RISER RINGS W/GASKET
  12"  (I.D.)  12"  AS REQUIRED  6" HDPE PIPE
  2

  Utica
  TOP SLAB IS

  8"
  TYP.
  STEEL REINFORCED TO MEET
  12"

  12"
  OR EXCEED HS-20 LOADING.

  ECCENTRIC CONE
  1

  Buffalo
  12"

  (IF SPECIFIED)
  (I.D.)  12"
  72" DIA. MIN.

  SECTION
  .  OR AS REQ'D
  DIA
  O.D.

  TOP OF PIPE ZONE

  )
  D.
  (I.
  6" HDPE 90 DEGREE ELBOW

  12"
  DET. A  (REPLACE WITH TEE FOR INLINE DRAINS)
  (6"MIN.)  1  NOTE: ECCENTRIC CONE SECTION SHALL BE USED UNLESS  ALTERNATE TOP SLAB
  1/3 I.D. (12"MAX.)  DEPTH WARRANTS TOP SLAB PER MANUFACTURER
  .
  DIA

  O.D.

  )
  D.
  6" HDPE PIPE, SEE PLAN FOR SLOPE

  (I.
  NOTES:  (6"MIN.)  NOTE:
  A. PIPE INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURERS  1/3 I.D. (12"MAX.)  SEE TYPICAL TRENCH SECTION FOR BEDDING REQUIREMENTS
  RECOMMENDATIONS.  GASKETED  STEEL REINFORCED COPOLYMER
  JOINT (TYP.)  POLYPROPYLENE PLASTIC STEP
  B. TRENCHING OPERATIONS SHALL INCLUDE ALL NECESSARY DEWATERING.
  C. TRENCH DETAILS ARE ONLY SHOWN FOR PURPOSES OF MATERIAL  TYPICAL YARD DRAIN DETAIL

  RISER SECTION
  PLACEMENT AND MAXIMUM PAY LIMITS.  NOTES:

  (IF REQ'D)
  A. PIPE INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURERS  NOT TO SCALE
  D. AN OSHA APPROVED MOVABLE PROTECTIVE TRENCH SHIELD SHALL  RECOMMENDATIONS.
  BE USED IN ALL UNSHEETED TRENCH AREAS.  B. TRENCHING OPERATIONS SHALL INCLUDE ALL NECESSARY DEWATERING.  72" DIA. MIN.  5" MIN. OR
  OR AS REQ'D  AS REQ'D

  West Seneca Exchange
  EXTERIOR CLEANOUT @ GRADE
  MATERIALS  C. TRENCH DETAILS ARE ONLY SHOWN FOR PURPOSES OF MATERIAL  DETAIL A  J.R. SMITH #4251-U W/ VANDAL-
  PLACEMENT AND MAXIMUM PAY LIMITS.  PROOF SCREWS OR APPROVED EQUAL  CAP
  PIPE BEDDING MATERIAL (NYSDOT 1985 EDITION)  D. AN OSHA APPROVED MOVABLE PROTECTIVE TRENCH SHIELD SHALL
  BE USED IN ALL UNSHEETED TRENCH AREAS.  TOP COURSE

  Slade Ave, Ridge Rd & Orchard Park Rd
  1  NO. 1 CRUSHED STONE OR CRUSHED GRAVEL WITH A GRADATION CONFORMING WITH NYSDOT SECTION 703-02. THE MATERIAL  EXPANSION JOINT
  BINDER

  2"
  SHALL BE WELL GRADED WITH NO PARTICLES LARGER THAN ONE INCH AND HAVING A MAXIMUM GRADATION MEETING THE LIMITS
  DESCRIBED IN THE SPECIFICATIONS. THE BEDDING SHALL BE COMPACTED IN 6" LIFTS WITH EQUIPMENT ACCEPTABLE TO THE PIPE  GENERAL NOTES:  WITH FIBERBOARD

  12" MIN.
  MATERIALS
  MANUFACTURER.  1. REINFORCED STEEL TO CONFORM TO LATEST A.S.T.M. A185  STONE BASE  4000 PSI CONCRETE ENCASE
  PIPE BEDDING MATERIAL (NYSDOT 1985 EDITION)  SPEC. 0.12 SQ. IN./LINEAL FT. AND 0.12 SQ. IN. (BOTH WAYS)
  PIPE, SEE PLAN  TO FULL DEPTH OF FRAME
  IN BASE SLAB.
  NO SLAG SHALL BE ALLOWED FOR MATERIAL  1  NO. 1 CRUSHED STONE OR CRUSHED GRAVEL WITH A GRADATION CONFORMING WITH NYSDOT SECTION 703-02. THE MATERIAL
  1  FOR SIZE & INVERT
  SHALL BE WELL GRADED WITH NO PARTICLES LARGER THAN ONE INCH AND HAVING A MAXIMUM GRADATION MEETING THE LIMITS  2.  CONCRETE COMPRESSIVE STRENGTH - 4000 PSI MINIMUM.

  BASE SECTION
  TYPE 2 CRUSHED STONE OR CRUSHED GRAVEL WITH A GRADATION CONFORMING WITH NYSDOT SECTION 304-2.02 TYPE 2. THE  DESCRIBED IN THE SPECIFICATIONS. THE BEDDING SHALL BE COMPACTED IN 6" LIFTS WITH EQUIPMENT ACCEPTABLE TO THE PIPE
  2  6" FOR IN-LINE CLEAN-OUT
  MATERIAL SHALL BE WELL GRADED WITH NO PARTICLES LARGER THAN TWO INCHES AND HAVING A MAXIMUM GRADATION MEETING THE  MANUFACTURER.  3.  MANHOLE DESIGN SPECIFICATIONS TO CONFORM TO LATEST

  SEE PLANS
  12" MIN.
  LIMITS DESCRIBED IN THE SPECIFICATIONS. THE BEDDING SHALL BE COMPACTED IN 6" LIFTS WITH EQUIPMENT ACCEPTABLE TO THE PIPE  A.S.T.M. C478 SPEC. FOR PRE-CAST REINFORCED CON-CRETE  SELECT FILL  8" FOR END OF LINE LAMPHOLE

  VARIES
  MANUFACTURER.  MANHOLE SECTIONS.
  NO SLAG SHALL BE ALLOWED FOR MATERIAL  1

  West Seneca New York
  4.  SINGLE POUR MONOLITHIC BASE SECTION.
  2  BACKFILL MATERIAL SHALL BE NATIVE SOIL CONTAINING NO UNSUITABLE MATERIAL COMPACTED IN 6" LIFTS.
  NO SLAG SHALL BE ALLOWED FOR MATERIAL  2
  © CARMINA WOOD DESIGN

  5.  MANHOLE TO BE COATED ON OUTSIDE WITH BITUMASTIC

  8" THK.
  SEALER.
  FLOW

  STORM SEWER TRENCH SECTION  STORM SEWER TRENCH SECTION
  IN PAVED AREAS  IN UNPAVED AREAS  SEE PLANS FOR

  6" MIN.
  SEWER SIZES
  NOT TO SCALE  NOT TO SCALE  FRAME OD + 2'
  COMPACTED TYPE 2 R.O.C. STONE BASE,
  NYSDOT ITEM 304.02

  6'
  STANDARD END SECTIONS
  TYPICAL STORM MANHOLE DETAIL  LAMPHOLE/CLEANOUT IN PAVEMENT/SIDEWALK
  NOT TO SCALE
  NOT TO SCALE

  Date
  2'

  RIM ELEV. - VARIES  4" Ø PERFORATED HDPE DRAIN PIPE, EXTEND 5' FROM CB, CAP END PIPE SHALL
  HEAVY DUTY FRAME  BE SURROUNDED WITH 4" MIN. NYSDOT NO.1 WASHED STONE OR GRAVEL ON
  OF PIPE

  (SEE PLAN), PROVIDE
  WIDTH

  STORM PIPE W/END SECTIONS  AND GRATE, NEENAH  RISER SECTIONS TO  ALL SIDES, SLOPE OF PIPE SHALL MATCH SUBGRADE SLOPE (TYP. ON 4 SIDES
  (SEE PLANS FOR SIZE AND TYPE)  OF CB, NOT REQUIRED ON SIDES WHERE PIPES ENTERING/EXITING HAVE 2' OR
  R4832B, HS20-44,  ACHIEVE RIM ELEV.
  BICYCLE PROOF  LESS COVER)

  TOP OF PAVEMENT
  2'

  No. Description
  TOP OF BANK

  REVISIONS:
  OF BANK
  BOTTOM

  2'-0"
  PAVEMENT SUBBASE
  PLAN VIEW
  6"  2'-0" *  6"
  PRECAST CONCRETE  SURROUND STONE WITH GEOTEXTILE DRAINAGE
  CATCH BASIN UNIT,  MIN.
  STANDARD END SECTIONS  FABRIC, TYPAR OR EQUAL
  KISTNER CB-2436
  OR EQUAL  INVERT ELEV.-
  3' MIN.  PLACE STONE FILL  VARIES
  1  HALFWAY UP THE SIDE OF  STORM PIPE-
  PIPE UNLESS OTHERWISE NOTED  SEE PLAN  SIZE VARIES
  (SEE PLAN)
  12" OF STONE FILL
  SEE PLAN FOR TYPE

  12" SUMP

  Sealed 07/20/2026
  NEW CULVERT W/END SECTIONS
  (SEE PLANS FOR SIZE AND TYPE)  6'-0"

  6"
  6" COMPACTED NYSDOT
  TYPE 2 R.O.C. STONE BASE
  NYSDOT ITEM 304.12

  UNDISTURBED
  EARTH  *NOTE: USE UP TO 18" PIPE, FOR LARGER PIPES USE STORM MH, SEE DETAIL
  PIPE BEDDING, SEE
  TRENCH SECTION
  ELEVATION
  NOTE: LIMITS OF STONE SHOWN ARE
  MINIMUMS, PLAN MAY INDICATE GREATER
  LIMITS  TYPICAL PRECAST CATCH BASIN
  NOT TO SCALE

  DRAWING NAME:

  TYPICAL PIPE OUTLET W/ END SECTION & RIP RAP  Storm Drainage
  NOT TO SCALE  Details

  Date:  07/20/26
  Drawn By:  C. Wood
  Scale:  As Noted
  DRAWING NO.

  C-305
  Project No:  24-4113

  Page 1062 of 1174