Our response  The impact
Working with our subconsultant, GHD installed 14  The model will continue to serve as a living inventory of
flowmeters and four rain gauges within the southern  the interceptor system. GHD will continue to work with
portion of the Town of Lockport and the Town of  NCSD to keep the model updated with any changes
Pendleton to focus model recalibration in that area.  made to the sewers or pump stations.
Using the computed-based, system-wide PCSWMM
  The model will be used for predictive scenarios and
hydraulic model created by GHD in 2016, this data
  future planning, especially in the case for construction of
will be used to recalibrate the model in areas
  new subdivisions in Lockport, NY.
upstream of the metered sewers using the newly
collected information. Inflow/infiltration (I/I) will be
modeled using recalibrated RTK unit hydrographs;
the industry standard method for modeling I/I. Pump
stations in the area of interest will be remodeled
based on actual operating parameters including
pumps curves, pump on elevations, and pump off
elevations.
In the future, this updated model will be utilized to
conduct Downstream Capacity Analyses (DSCA),
which aim to identify areas of concern within the
sewer system and pinpoint potential capacity issues
resulting from new developments and ongoing I/I
removal efforts by the District and/or member towns.
Particular attention will be given to the downstream
capacity of South Lockport’s interceptor system to
address any capacity issues arising from the
proposed and ongoing subdivision construction.
Pump capacity at the various pump stations will also
be investigated.
Model results will be presented in an engineering
report that describes calibration methods and model
statistics following the outline in the Chartered
Institute of Water and Environmental Management
Code of Practice for Modelling Urban Drainage
Systems.