Text · page 45 of 110
Read the whole document on one page (all 110 pages, each with its own heading)
General Assumptions Description Density Units Lightning Load 1.0 VA/sq-ft Receptacle Load 1.0 VA/sq-ft Electric Heating Load (heat pumps, hot water) 12.0 VA/sq-ft Air-Handling Equip 1 CFM/sq-ft. Pumping Equipment 50 BTU/hr/sq-ft Elevator 25** HP* EV Charging 6,700** VA Service Factor 125 % *To be conservative, we will assume 1HP = 1kW **Taken from previous projects Page 45 of 110