Area  Load
  Density  Units
Description  (sq-ft)  (kVA)
Gross Floor Area:  75,803

Lighting Load  1  VA/sq-ft  75,803  76
Receptacle Load  1  VA/sq-ft  75,803  76
Elec Heating Load  12  VA/sq-ft  75,803  910
  Typical Mechanical Conditions
  Conv.
  Static  Conv.
  Area  Fan Effic. Factor  Load (HP  Service
  Airflow  Press  Factor
  (sq-ft)  (unitless) (PSI/ in  or kW)  Factor
  (in WC)  (HP/CFM)
  WC)
Air-Handling Equipment  1  CFM/sq-ft  75,803  75,803  3  0.5  5.2  0.00095  72  125%  90

  Area  Heat Load  Delta-T  Flow
  (sq-ft)  (BTU’s/hr)  (Degrees)  (GPM)
  BTU/hr/sq-
  50  75,803  3,790,000  20  379  0.01010  4  125%  5
Pumping Equipment  ft

  Units
Elevator  25  HP  0  25  125%  0
EV Chargers  6.7  kW  5  33.5  125%  42

  TOTAL  1,199