ARM Hydrant Flow Test Inquiry -- Hydrant: M16G42 Test Date/Time: 6/17/2019 11:35 CHI095-B Address: 431 QUAKER RD Side: S Location: 1ST E/O JEWETT HOLMWOOD RD AURORA Size of Main/Branch: 20"/6" Fire District: 24020 FIRE PROTECT DIST 1 Water District: 059 ECWA AREA-TOWN OF AURORA ¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯ Performed By: AMM Comments: HYDRANT FLOW TEST REQUESTED BY ERIC DANIEL, C&S COMPANIES PHONE: 847-1630; EMAIL: [email protected] ¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯ Dischrge Coef: .90 Elvtn Usgs(ft): Static(psi): 81 Residual(psi): 64 Required Residual Pressure(psi): 20 Gallons Used..: 3,330 Total Flow(gpm): 1,113 Flow at Reqd Resid Pressure: 2,219 Flow Hydrants: C Flow Hyd Flow Hydrant Address Main/Brnch Nzle Size Pitot Flow Comments M16 G41 OP 25 JEWETT HOLMWOOD 8"/6" 1: 2.50 44.0 1,113 1ST HYD SW/O QUAKER RD 2: 3: Tot Flow: 1,113 ¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯ Bottom I=Flow Hydrant Inquiry ENTER=Continue F3=Exit F6=Maintain Test F7=Test Hydrant Inquiry F15=Print Test Information