Draft Wales Chapter #197 Battery Energy Storage Systems Initial Draft (dated 10/26/26) System Inspection Checklist. The Battery Energy Storage System inspection Checklist provides an overview of common points of inspection that the applicant should be prepared to show compliance. Plans shall include a note that a plug-in type back-fed circuit breakers connected to an interconnected supply shall be secured in in accordance with (NEC 408.36(D)). Provide a permanent plaque or directory denoting all electric power sources on or in the premises, which shall be installed at the main service panel and at all locations of all electric power production sources capable of being interconnection (e017 NEC. N 106. 11). One or Three-Line Diagram Show grounding and bonding for the battery: energy storage: system, including the ground return path. Q vi. Show method of interconnection. Vii. Show overcurrent protection method and rating when required. viii. include detailed wiring information for all new cirouits,including: Conductor size/type ne Number of conductors xi. Conduit size Xi. Conduit type : xiii. Show all disconnection means. : xiv. Show ratings (voltage; ‘ampacity ; ‘environmental, etc) for new and existing service equipment... XV. Specifications and installation: ‘instructions xvi. Prepackaged and pre-engineered battery energy storage systems shail be. installed in accordance with their listing and the manufacturer's instructions. - xvii Provide specifi cation sheets and installation instructions for the ». following: ‘equipment: xviii Batteries a xix. _ Inverter. ~ “Transformer or autotransformer Transfer switch(es) ESS support or racking Converters Interconnecting cables and connectors Management system, including charge controller(s) XXVi. Panelboards XXvil. HVAC/thermal management system xXxviil. Fire rated material XXX, Storage batteries and battery storage systems shall comply with the following: Storage batteries shall be listed in accordance with UL 1973 Prepackaged and pre-engineered battery energy storage systems shall be listed in accordance with UL 9540. Exception: Lead-acid batteries are not required to be listed TOWN OF WALES — BATT ERGY STORAGE SYSTEMS 6