Draft Wales Chapter #197 Battery Energy Storage Systems
  Initial Draft (dated 10/26/26)

  System Inspection Checklist. The Battery Energy Storage System
  inspection Checklist provides an overview of common points of inspection
  that the applicant should be prepared to show compliance.
  Plans shall include a note that a plug-in type back-fed circuit breakers
  connected to an interconnected supply shall be secured in in accordance
  with (NEC 408.36(D)).
  Provide a permanent plaque or directory denoting all electric power
  sources on or in the premises, which shall be installed at the main
  service panel and at all locations of all electric power production
  sources capable of being interconnection (e017 NEC.  N  106. 11).
  One or Three-Line Diagram
  Show grounding and bonding for the battery: energy storage: system,
  including the ground return path.  Q
  vi.  Show method of interconnection.
  Vii.  Show overcurrent protection method and rating when required.
  viii.  include detailed wiring information for all new cirouits,including:
  Conductor size/type  ne
  Number of conductors
  xi.  Conduit size
  Xi.  Conduit type  :
  xiii.  Show all disconnection means. :
  xiv.  Show ratings (voltage; ‘ampacity ; ‘environmental, etc) for new and
  existing service equipment...
  XV.  Specifications and installation: ‘instructions
  xvi.  Prepackaged and pre-engineered battery energy storage systems shail
  be. installed in accordance with their listing and the manufacturer's
  instructions.  -
  xvii  Provide specifi cation sheets and installation instructions for the
  ». following: ‘equipment:
  xviii  Batteries a
  xix. _ Inverter.
  ~ “Transformer or autotransformer
  Transfer switch(es)
  ESS support or racking
  Converters
  Interconnecting cables and connectors
  Management system, including charge controller(s)
  XXVi.  Panelboards
  XXvil.  HVAC/thermal management system
  xXxviil.  Fire rated material
  XXX,  Storage batteries and battery storage systems shall comply with the
  following:
  Storage batteries shall be listed in accordance with UL 1973
  Prepackaged and pre-engineered battery energy storage systems shall
  be listed in accordance with UL 9540. Exception: Lead-acid batteries
  are not required to be listed