Fixtures are organized into two occupancy groups operating in non-overlapping time windows (Section 5). Load values are public-use figures per Table E103.3(2). Group A — Daytime occupancy (incl. brewery operations) Fixture (public) WSFU ea. Qty Subtotal WSFU Water closet, flush tank 5 2 10 Lavatory 2 2 4 Kitchen / break sink (offset by brewery fill) 4 1 4 Group A total 18 WSFU Group B — Evening occupancy Fixture (public) WSFU ea. Qty Subtotal WSFU Water closet, flush tank 5 2 10 Lavatory 2 2 4 Service / mop sink 3 1 3 Group B total 17 WSFU An exterior hose bibb serves maintenance use only, operated outside occupied restroom peaks; it is non-coincident with the interior peak and not additive. There is no simultaneous irrigation demand. 5. Demand Analysis — Non-Coincident Use Fixture units are converted to a probable peak demand via Hunter's curve, Table E103.3(3), for a flush-tank system. Demand basis Total WSFU Peak demand Design — non-coincident, governing group (Group A) 18 18.8 gpm Basis of the non-coincident demand. Group A (daytime, including brewery operations) and Group B (evening) operate in separate, non-overlapping time windows. Simultaneous use of both groups is not possible: the facility does not brew during events, so an evening event cannot coincide with daytime brewery / kitchen demand. The service therefore never carries the two groups' combined load — the peak instantaneous demand is that of the single larger group, Group A at 18 WSFU → 18.8 gpm, not the arithmetic sum. Within Group A, the ~45-minute brewery fill occurs while the kitchen is offline and directly offsets the kitchen demand (Section 4), so it is not additive. This non-coincident basis is applied in addition to the simultaneity probability already embedded in Hunter's curve. 6. Service Capacity — Velocity Check Velocity governs the 1" service and is independent of available pressure: V = 0.4085 × Q ÷ d², d = 1.025 in. Demand basis Flow Velocity in 1" service Design — non-coincident 18.8 gpm 7.31 ft/s — WITHIN 8 ft/s ✓ Simultaneous A + B (precluded — reference) 24.9 gpm 9.68 ft/s — over 8 ft/s At the design (non-coincident) demand the service operates at 7.31 ft/s — 91% of its velocity ceiling, within limits. The simultaneous condition, precluded by the operating configuration, is shown for reference only. 7. Pressure Balance & Residual Pressure Per IPC Appendix E, source-to-building losses at the 18.8 gpm design demand are subtracted from available pressure to confirm adequate residual pressure remains. Component psi Running Available min. daily pressure at main 67.0 67.0 Page 41 of 84