General - Poles  Page 2 of 2 in this chapter

  7)  When a pole cannot be immediately set, a hole covering will be placed to prevent any disturbances of the hole (see Figure
  2).
  8)  Allholes are to be dug straight down. All backfill is to be power tamped and compacted in 1-foot lifts, If the excavated
  material is found to be unsuitable for use as backfill, use bank run gravel or a well-graded crushed stone with #1 crushed
  stone as maximum  size.
  9)  On side hills, hole depth shall be measured from the downhill side of hole. Pole in sloping ground shall be set to the depth
  in Figure 3.
  10)  In cases where a new pole is more than 5 feet taller than the existing adjacent pole, the immediately adjacent poles
  should be changed so that there is no more than a 5-foot height difference from pole to pole to prevent uplift.
  a.  The new adjacent pole(s) being set shall be the correct height for the area but framed to comply with the 5’
  height difference rule.
  b.  For example, a new 50’ recloser pole will be set in an area with 40’ poles.
  i.  ifthe correct height pole for this area is 45’, the pole next to the recloser pole on each side must be
  replaced with a 45’ pole, framed as a 45’ pole, The other 40’ poles may remain in service. The poles
  heights comply with the 5’ height difference rule between the three poles one each side (Recloser pole:
  50’, 2"¢ pole: 45’, 3° pole: 40’).
  ii,  tf the correct height pole for this area is 50’, the pole next to the recloser pole on each side must be
  replaced with a 50’ pole, framed as a 45’ pole. The other 40’ poles may remain in service. The pole
  framings comply with the 5’ height difference rule between the three poles one each side (Recloser
  pole: framed at 50’, 2" pole: framed at 45’, 3 pole: framed at 40’).

 Mole Covered w/ Portion of
 excavated Material on q.,
 Covering

 Hole Covering
  SLOPE OF
  FINISH GRADE
  Ze
  Be

 Note: For poor soll  Hole  |  :  THIS SHALL BE THE
 conditions ar wet hole, an  SET DEPTH FROM
 appropriately sized caisson  Hole Diameter  PAGE 1, TABLE 4
 is to be Installed in the hole.

  Figure 2  Figure 3

  AVANGRID  DISTRIBUTION  .  .
ENGINEERING  CONSTRUCTION  STANDARDS  Wood  Pole  Installation

  DSN: GY  | DR: CR  Page2 of 2 in this DCS
  CK:  ES  MACRO #:
  UPDATES TO STANDARD DRAWING AND MACROS  APP:  XX  DCS #:  REY.
REV,  DATE  BY  DESCRIPTION  APP. | DATE:  01/23/24  DCS-OH-GC-02-230  0

  internal Use